Startup
During initial commissioning, the presence
detector creates a room image. The room
must be free of movement for 2 to
2.5 minutes for this.
Note:
An image of the room is also created if
reach or mounting height is changed.
The ETS can adjust the sensitivity of the
True Presence ® Multisensor from 1 (=
low) to 9 (= high).
The functions to be used (activated) are
set in the "General Settings" parameter
window using the ETS.
Note:
You will find an application
description at knx.steinel.de.
1. Issue physical address and generate
application program in the ETS.
2. Load the physical address and appli-
cation program into the multisensor.
When you are prompted, press the
programming button A (Fig. 4.1).
Smart Remote app
To read off and activating the program-
ming mode of the multisensor via smart-
phone or tablet, you must download the
STEINEL Smart Remote app from your
app store. You will need a Bluetooth-
capable smartphone or tablet.
Android
iOS
LED function
Initialisation: LED white
Normal mode: LED OFF
Bluetooth connection active: LED blue
Error: LED red
Programming mode:LED green
Application not configured or wrong:
LED lights up orange
7. Accessories
Surface-mounting adapter
(EAN: 4007841 063870)
8. Maintenance / care
The product requires no maintenance.
The multisensor can be cleaned with a
damp cloth (without detergents) if dirty.
– 15 –