L & XL Variante
↻ Time required for DC connection: 15 min
↻ Connection cable with 2 x 1 cores is provided on the unit.
1 Undo the cable fitting [
2 Remove the outer cladding of the DC cables.
3 Pass the DC cables through the cable fittings into the connection compartment.
4 Fit DC lines with an M10 ring cable lug [max. width b 1,10 In ].
5 Screw the negative (-) cable end onto the DC connection according to the polar-
ity of the battery [
W17 /
6 Screw the positive (+) cable end onto the DC+ fuse holder according to the po-
larity of the battery [
W16 /
7 Check secure fit of all connected cables.
8 Ensure that the polarity is correct.
9 Tighten cable fittings [
4.4.2 Without precharge unit
CAUTION
Danger caused by exceeding the inrush current.
The device does not have a inrush current limiter on the DC side. Exceeding the maximum permissible inrush
current of 300A can lead to destruction of the device.
The inrush current must be limited to a max. current of 300A using external means. The DC input ca-
pacity of the device is approx 550µF.
DC link may still be charged link after disconnecting the device from the battery. The limitation of the
inrush current must also be ensured in this scenario.
Failure to observe these instructions may result in damage to the device which is not covered by the
warranty.
M variant
↻ Connection cable with 2 x 1 strands already on the device.
1 Undo the cable fitting [
2 Remove the outer cladding of the DC cables.
3 Pass the DC cables through the cable fittings into the connection compartment.
4 Fit DC lines with an M10 ring cable lug [max. width b 1,65 In].
5 Screw the negative (-) cable end onto the DC connection according to the polar-
ity of the battery [
W17 /
6 Screw the positive (+) cable end onto the DC+ fuse holder according to the po-
larity of the battery [
W16 /
7 Check secure fit of all connected cables.
8 Make sure that the polarity is correct, and that the inrush current is ensured at
max. 300A.
9 Tighten cable fittings [
4.5
Inserting the overvoltage protection
Information on the overvoltage protection: See
battery inverter/manual" category.
4.6
Creating equipotential bonding
NOTE
Depending on the local installation specifications, it may be necessary to earth the device with a second
ground connection. To this end, the threaded bolt on the underside of the device can be used.
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
W_46]
265.52 In-Ibs ].
265.52 In-Ibs].
W_46 /
88.50 In-Ibs ].
W_46]
265.52 In-Ibs ].
265.52 In-Ibs].
W_46 /
88.50 In-Ibs ].
http://www.kaco-newenergy.com/de/downloads
M10
1,65 In
M10
Fig. 5: DC connection L version
M10
1,65 In
M10
Fig. 6: DC connection XL version
M10
1,65 In
M10
Fig. 7: DC connection M version
in the "Hybrid and
Side 139