L & XL Variante
↻ Time required for DC connection: 15 min
↻ Connection cable with 2 x 1 cores is provided on the unit.
1 Undo the cable fitting [
2 Remove the outer cladding of the DC cables.
3 Pass the DC cables through the cable fittings into the connection compartment.
4 Fit DC lines with an M10 ring cable lug [max. width b 1,10 In ].
5 Screw the negative (-) cable end onto the DC connection according to the polar-
ity of the battery [
W17 /
6 Screw the positive (+) cable end onto the DC+ fuse holder according to the po-
larity of the battery [
W16 /
7 Check secure fit of all connected cables.
8 Ensure that the polarity is correct.
9 Tighten cable fittings [
4.4.2 Without precharge unit
CAUTION
Danger caused by exceeding the inrush current.
The device does not have a inrush current limiter on the DC side. Exceeding the maximum permissible inrush
current of 300A can lead to destruction of the device.
›
The inrush current must be limited to a max. current of 300A using external means. The DC input ca-
pacity of the device is approx 550µF.
›
DC link may still be charged link after disconnecting the device from the battery. The limitation of the
inrush current must also be ensured in this scenario.
›
Failure to observe these instructions may result in damage to the device which is not covered by the
warranty.
M variant
↻ Connection cable with 2 x 1 strands already on the device.
1 Undo the cable fitting [
2 Remove the outer cladding of the DC cables.
3 Pass the DC cables through the cable fittings into the connection compartment.
4 Fit DC lines with an M10 ring cable lug [max. width b 1,65 In].
5 Screw the negative (-) cable end onto the DC connection according to the polar-
ity of the battery [
W17 /
6 Screw the positive (+) cable end onto the DC+ fuse holder according to the po-
larity of the battery [
W16 /
7 Check secure fit of all connected cables.
8 Make sure that the polarity is correct, and that the inrush current is ensured at
max. 300A.
9 Tighten cable fittings [
4.5
Inserting the overvoltage protection
Information on the overvoltage protection: See
battery inverter/manual" category.
4.6
Creating equipotential bonding
NOTE
Depending on the local installation specifications, it may be necessary to earth the device with a second
ground connection. To this end, the threaded bolt on the underside of the device can be used.
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
W_46]
265.52 In-Ibs ].
265.52 In-Ibs].
W_46 /
88.50 In-Ibs ].
W_46]
265.52 In-Ibs ].
265.52 In-Ibs].
W_46 /
88.50 In-Ibs ].
http://www.kaco-newenergy.com/de/downloads
M10
1,65 In
M10
Fig. 5: DC connection L version
M10
1,65 In
M10
Fig. 6: DC connection XL version
M10
1,65 In
M10
Fig. 7: DC connection M version
in the "Hybrid and