Pressure Settings:
The general failure cannot be adjusted to a value above the superior limit of the sensor's range.
The alarm cannot be adjusted to a value above (Max.P. -0,2 bar) or below (P4 + 0,2 bar)
The unload cannot be adjusted to a value above (Alarm P. -0,2 bar) or below (P3 + 0,2 bar)
The load pressure cannot be adjusted to a value above (P2-0,2 bar) or below 5,0 bar.
Pressure and Temperature Units:
Selects the units for the presented values. The control operates internally with mBar (0,001 bar) and Celsius (0,001ºC). The presented values
are calculated based on the internal operation values.
Language: The language is applied to the text that appears in the lower part of each menu.
This text can be disabled by selecting the value 0 (zero) in the settings.
4.4.4 - P02 Errors List Menu
P02
+
15
------
01
E:0020
02
E:0040
03
E:0080
FILTRO DE ÓLEO
P02
01.01
E:0020
0hrs
12/07/2011
FILTRO DE ÓLEO
Item Nº
Description
01
Registered error n° 1
02 a 15
Registered errors n° 2 a n° 15
4.4.5 - P03 Stops Menu
The settings that determine the level or condition in which a shutdown fault is created.
Item Nº
Description
01
Shutdown Temperature
02
Maximum outlet pressure
03
Maximum internal pressure
04
Maximum differential pressure
05
Internal control pressure
** the maximum outlet temperature limit can be higher when alternate temperature sensors are used.
High Level of Differential Pressure:
Will be enabled if the condition remains above the adjusted limit for longer than the delay time (see menu 07) and the outlet temperature is
higher than 50°C.
Minimum Internal Pressure Level:
The internal pressure is checked after the compressor start-up. If the detected pressure is lower than the adjusted limit, a shutdown error
will be created. This function was designed to offer protection against incorrect speed of the motor, or internal connection or piping failure.
The list of errors page contains the last 15 fault codes in chronological order. The most recent
fault is recorded as item 01. If all the 15 fault registers are full and a new fault event occurs, the
new fault status is added as item 01, all the item register entries move to one number above,
and the item 15 register entry is lost.
Press ENTER to see all the details of a register entry. The register item screen will show the
fault code together with the symbolical identification and the operating hours, recorded time
and date of the moment the fault occurred. The types of fault are identified by the initial letter
of the fault code: E = Shutdown/General Failure, A = Alarm/Warning, R = Operation/Load
Impediment. All these items are only for visualization.
10:15
Units
---
---
Units
°C / °F
bar/psi
bar/psi
bar/psi
bar/psi
Step
Mín.
Reading
---
Reading
---
Step
Mín.
1
8,0
0,1
7,0
0,1
7,1
0,1
Alarme + 0,2
0,1
0,0
91
Máx.
Display
---
01...E:0020
---
02 A 15
Máx.
Display
130
Td 115°C
16,0
Pd 10,0bar
16,0
Pd 11,0bar
5,0
∆P 1,0bar
0,3
Pr 0,3bar