Descargar Imprimir esta página

STEINEL PROFESSIONAL S 3360 COM1 Manual Del Usuario página 15

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 36
For mounting the IS 3180 on the wall, a condensation water drainage hole (Ø 5 mm
drill bit) is marked next to the rubber seal. This must be opened if necessary.
Connection examples (Fig� 4�2)
a Light without neutral conductor
b Light with neutral conductor
c Connection by means of two-circuit single-interruption switch for
manual and automatic operation
d Connection via two-way switch for manual override and automatic operation
Setting I: Automatic operation
Setting II: Manual operation, light permanently ON
Note:
The system cannot be switched OFF, it is only possible to select operation
via setting I or II.
a) Load, lighting max. 2000 W (refer to Technical specifications)
b) Sensor connection terminals
c) Indoor switch
d) Indoor two-circuit single-interruption switch, manual, automatic
e) Indoor two-way switch, automatic, light permanently ON
Connecting several sensors in parallel (not illustrated)
In this case, it is important not to exceed a sensor's maximum connected rating. In
addition, all units must be connected to the same phase. As many as 10 sensors can
be connected in parallel.
Note:
The cable between two sensors must be no more than 50 m in length.
5� Mounting
• Check all components for damage.
• Do not use the product if it is damaged.
• Select an appropriate mounting location, taking the reach and motion detection
into consideration.
Procedure for installing concealed power supply lead (Fig� 5�1)
Procedure for installing surface-mounted power supply lead (Fig� 5�2)
IS 3360, IS 3360 MX Highbay, IS 345, IS 345 Highbay
Procedure for installing concealed power supply lead (wall mounting) IS 3180
(Fig� 5�3)
28
• Switch OFF power supply.
• Detach designer trim from sensor module.
• Disconnect sensor module from the load module.
• Connect to mains power supply.
– Surface-mounted power supply lead (Fig� 5�4)
– Concealed power supply lead (Fig� 5�5)
• Insert fastening screw and mount load module.
Limiting reach
The detection zone can be optimised to suit requirements.
– By adjusting the lens. (Fig� 5�8 / 5�10)
– By using the half-round clip-on shroud. (Fig� 5�11)
Note:
To limit reach, the sensor module must be detached from the load module.
• To activate the required reach, undo the screws or completely remove them.
• Move lens into required zone.
• The half-round clip-on shroud provided can be used for masking out any number
of lens segments to shorten reach as required.
• Afterwards, fix the lens in place with the screws.
Detection zone/reach
IS 3360 (Fig� 5�6)
IS 3360 MX (Fig� 5�7)
Mounting height
Reach (tangential)
14 m
10 m
9 m
14 m
6 m
16 m
2.8 m
18 m
IS 345 (Fig� 5�8)
IS 345 MX (Fig� 5�9)
Mounting height
Reach (tangential)
14 m
30 m × 4
10 m
25 m × 4
8 m
20 m × 4
6 m
15 m × 4
4 m
10 m × 4
29

Publicidad

loading

Este manual también es adecuado para:

Is 3360 mx com1Is 345 com1Is 345 mx com1Is 3180 com1