Analog outputs are not available in transmitters that are powered with Power over Ethernet
(PoE).
Use the touchscreen or web interface to change the output mode (for example, 0 ... 5 V or
4 ... 20 mA) and scaling of the analog outputs.
+
CH1
RS-485
PROBE
1
+
CH2
24 VOUT
+
ANALOG
CH3
INPUT
+
CH4
M20×1.5
Table 8 Analog output terminals
Terminal
Function
CH1 +
Analog output channel 1 +
CH1 -
Analog output channel 1 -
CH2 +
Analog output channel 2 +
CH2 -
Analog output channel 2 -
CH3 +
Analog output channel 3 +
CH3 -
Analog output channel 3 -
CH4 +
Analog output channel 4 +
CH4 -
Analog output channel 4 -
Ethernet connector and lead-through
You must use a shielded cable to meet the rated EMC performance of the device.
Before connecting wires or cables, make sure that the transmitter is powered off.
VS
2
For the M20×1.5 cable gland ordered
together with the transmitter from Vaisala,
the cable diameter is 5.0 ... 8.0 mm
(0.20 ... 0.31 in). Tightening torque for the
cable gland is 8 Nm.
For the M20×1.5 cable gland with split
bushing, the cable diameter is 7 mm
(0.28 in).
Notes
Max. wire size: 2.5 mm
2
(14 AWG)
15