SETTING OPERATIONAL PARAMETERS (INSTALLER LEVEL)
Index - String
MIN value
0 °C
0
Index - String
MIN value
0
1
Index - String
MIN value
-20 °C
2
Index - String
MIN value
0
3
Threshold for reactivation after shutdown Force-Off
MAX value
If the parameter value rin = 4 (parameter 8 of the Installer menu), then this is a probe storage system, this parameter
30 °C
indicates how much lower the threshold of Force-Off so as to prevent the compressor is reactivated after the interven-
tion of Force-Off dynamic extinguished soon after.
Configuration of the heating cable (ANK only)
MAX value
Setting the output to which the heating cable is connected:
0- no heating cable
2
1- heating cable on the CPA output (the parameter (0) of the menu with password=72 "according to CP must be 0")
2- heating cable on the VGC output if not used (the configuration of the dip switches must be: DIP1 = ON, DIP2=ON,
DIP5=ON, DIP8=OFF, DIP9=OFF)
Heating cable setpoint (ANK only)
MAX value
Heating cable activated with an external air temperature lower than the value of this parameter. Heating cable deac-
10 °C
tivated with an external air temperature higher than the value of this parameter, plus 1.0° hysteresis.
Thermostat pump switch-off
MAX value
0 = the pump continues to function when the set point temperature is reached.
1 = the pump switches off when the set point temperature is reached (when this option is selected, the adjustment is
1
automatically activated on the basis of the input temperature). This parameter is only visible with the adjustment on
the basis of the input temperature (parameter (0) =1 or 2).
Parameter function
Parameter function
Parameter function
Parameter function