Reference
B1
Power supply 230V AC 50hz (Must be protected by a 30mA GFCI)
F1
Interface unit fuse (5x20mm ; 250V ; T3, 15A)
B2
230V ~ 50Hz output for pump relay
Dry contact input for pool cover (contact open = pool cover open / contact closed = pool cover
B3
closed)
B4
Dry contact outputs for backwash, heater and filtration status
B5
Dry contact inverter output for motorized solar valve.
B6
Connector for multispeed commands on Variable speed pumps
B7
Temperature sensor inputs (water temperature and solar temperature)
CT1
Control unit 1 connection.
CT2
Control unit 2 connection (optional)
In the next sections each input / output connection is explained individually.
The maximum cable section to be used on any of the connectors is 2.5mm2 (AWG 13)
B1 Power Supply
B2 Single Speed pump connection
Connect single speed pumps as indicated in the drawings below. The FiltOut Connection on the Interface module
connects to the contactor A1 and A2 terminal. The pump (single or 3 phase) gets it power supply over the contactor.
Never connect a pump directly onto the Interface module!
Single Phase
Pump
8
ControlPro
Connection
Connect mains power (230V 1~50Hz) to this
connector marked 'Power In' on the unit.
Make sure the circuit is protected by a
30mA GFCI
Always disconnect power on the
ControlPro and the systems
connected to ControlPro before and during any
intervention on the system.
3 Phase
Pump