6. INSTALLATION INSTRUCTIONS AND CONFIGURATION
The installation shall be performed by qualified personnel.
Please note the five safety rules!

6.1 Wall installation

For installation on the wall, the four housing screws must be removed from the cover. After-
wards, the front plate must be lifted - if necessary - the ribbon cable must be removed from
the electrical outlet. The subshell of the device can now be installed on the wall (assembly
material is included).

6.2 Sensor installation

The sensor reacts to water contact at the two metal contacts (the sensor circuit is closed).
The assembly height of the sensor defines, at what level the water detector will sound an
alarm. The sensor cable can be lengthened up to a 50-meter dual-wire cable, and five water
sensors can be connected per input in parallel.
6.3 Connection configuration
Important! The cables running to the water detector must be
surface-mounted and installed in a fixed, solid maner!
L
L
N
L
N PE
Operating voltage
230 V AC
50-60 Hz
Relay
8A/230V
Relay plug-in card
connection
N
PE
PE
S
G
Ö
Sensor 1
Float switch
Option:
9V battery
Sensor 3
Sensor 2
Sensor 4
Float switch
Float switch
Float switch