Installation Instructions
CAUTION!
The unit installed in the following places is likely to run abnormally. If unavoidable, please
contact the professional personnel at the appointed service center.
● Where is full of oil.
● Alkaline soil off the sea.
● Where there is sulfur gas (like sulfur hot spring).
● Where there are devices with high frequency (like wireless devices, electric welding
devices, or medical equipment).
● Special circumstances.
● Electric wiring
1. The installation must be done in accordance with the national wiring regulations.
2. Only the power cord with the rated voltage and exclusive circuit for the air conditioning
can be used.
3. Do not pull power cord by force.
4. The electric installation should be carried out by the professional personnel as instructed
by the local laws, regulations and also this manual.
5. The diameter of the power cord should be large enough and once it is damaged it must
be replaced by dedicated one.
6. The earthing should be reliable and the earth wire should be connected to the dedicated
device of the building by the professional personnel. Besides, the air switch coupled with
the leakage current protection switch must be equipped, which is of enough capacity and
of both magnetic and thermal tripping functions in case of the short circuit and overload.
Table 4
Models
GORBEA 2X1
GORBEA 3X1
Notes:
1. The specifications of the breaker and power cable listed in the table above are determined
based on the maximum power (maximum amps) of the unit.
2. The specifications of the power cable listed in the table above are applied to the conduit-guarded
multi-wire copper cable (like, YJV copper cable, consisting of PE insulated wires and a PVC
cable jacket) used at 40°C and resistible to 90°C (see IEC 60364-5-562). If the working
condition changes, they should be modified according to the related national standard.
3. The specifications of the breaker listed in the table above are applied to the breaker with
the working temperature at 40°C. If the working condition changes, they should be
modified according to the related national standard.
Power Supply
220-240V~,50Hz
220-240V~,50Hz
Capacity of the
Air Switch
16A
25A
48
Recommended Cord
(pieces×sectional area)
2
3×1.5mm
2
3×2.5mm