CABLEADO Y ENCENDIDO DEL MOTOR
- Only qualified mechanical or electrical personnel should perform wiring or maintenance on the blower
assembly
- Never run a centrifugal blower to atmosphere, as this can cause overloading and damage the motor. Always
check your installation to make sure the motor is running within the motor manufacturers specific amp ranges.
- Republic blowers are shipped with the belts removed. Motor rotation must be checked prior to installing
the belt! Running the blower/motor assembly backwards will cause improper performance and damage the
blower.
- With the belt removed, "bump" the power to determine rotation of motor.
- The blower should be rotating clockwise (CW) from the belt side of the blower, counter-clockwise (CCW) if
you are on the motor side or impeller side of the blower. Rotation arrows on the blower cast housing (Motor
Side) show correct rotation of impeller rotation. If the motor is going the wrong direction, then have your
qualified electrician change the direction of rotation.
- If the blower is allowed to run in the wrong direction, you could cause damage to the idler pulley assembly
spring or belt. Even in reverse, a centrifugal blower will still provide a substantial amount of airflow and
pressure, but it will not perform to your satisfaction.
Diagrama de cableado del motor
6 Lead
9 Lead
9 Lead
12 Lead
Alta tensión
Baja tensión
Alta tensión
Baja tensión
Alta tensión
Baja tensión
Alta tensión
Baja tensión
Media tensión
440
220
380-440
220
440
220
440
220
380
Baja tensión
Alta tensión