Configuration of the control panel

7.1. Configuration of delays.

The delays of the "Sounder relay output" and "Fault relay output" are configured using the
control keys on the control panel.
The time indication for these delays is displayed in binary code using the Battery Fault indicator,
CPU Fault, COM and Keyboard Access leds.
the
programmed
Note:
independently of the alarm comes from a detector, a
manual call point, or a combination of them.
Figure 8: led indicators used for delay time configuration.
The procedure is as follows:
1) Activate access level 2 (press the control keys once in the following order: Zone/Relay
selection, Reset/Autotest, Zone/Relay selection, Reset/Autotest).
2) Activate access level 3 (press the control keys once in the following order: Test mode,
Disable, Test mode, Disable).
3) Select the relay to which you wish to apply the delay using the control key Select
Relay.
4) Press the control key No delay in order to select the times. These are shown in the
following table along with the corresponding state of the indicator lamps:
Note: The first button indicates the current delay.
er
N
of pressings
Avería batería
H
Battery fault
Avería CPU
I
CPU fault
COM
J
Acceso Teclado
K
Keyboard Access
Sounder Relay
(minutes)
Fault Relay
(minutes)
Figure 9: Correlation between the N
Conventional Fire Detection and Fire Alarm Control Panels
CLVR02Z
/
delays
are
1
2
3
4
0
1
2
3
0
1
2
3
er
of pressings of the no delay control key, the state of the indication
leds and the configured delay times.
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - cofem@cofem.com - www.cofem.com
CLVR04Z / CLVR08Z / CLVR12Z
maintained
5
6
7
8
4
5
6
7
4
5
6
7
OFF
ON
9
10
11
12
8
9
10
10
8
9
10
10
39
13
10
10

Publicidad

loading

Este manual también es adecuado para:

Clvr04zClvr08zClvr12z