Ferroli BLUEHELIX B 32 K 50 Instrucciones De Uso, Instalación Y Mantenimiento página 43

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Switching the boiler off and on
Press the on/off button (detail 7 - fig. 1) for 5 seconds.
fig. 7 - Switching the boiler off
When the boiler is switched off, the electronic board is still powered. Domestic hot water
and heating are disabled The antifreeze system remains activated. To switch the boiler
on, press the on/off button (detail 7 - fig. 1) again for 5 seconds.
The boiler will be immediately ready to operate whenever domestic hot water is drawn
or in case of a room thermostat demand.
B
The antifreeze system does not work when the power and/or gas to the unit are
turned off. To avoid damage caused by freezing during long shutdowns in win-
ter, it is advisable to drain all water from the boiler, the DHW circuit and the
heating system water; or drain just the DHW circuit and add a suitable anti-
freeze to the heating system, as prescribed in sec. 3.3.
2.4 Adjustments
Summer/Winter Switchover
Press the summer/winter button (detail 6 - fig. 1) for 2 seconds.
The display activates the Summer symbol (detail 10 - fig. 1): the boiler will only deliver
domestic hot water. The antifreeze system remains activated.
To deactivate the Summer mode, press the summer/winter button (detail 6 - fig. 1)
again for 2 seconds.
Heating temperature adjustment
Use the heating buttons (details 3 and 4 - fig. 1) to adjust the temperature from a min. of
20°C to a max. of 80°C.
DHW temperature adjustment
Use the DHW buttons (details 1 and 2 - fig. 1) to adjust the temperature from a minimum
of 10°C to a maximum of 65°C.
2
1
3
0
4
2
1
3
0
4
fig. 8
2
1
3
0
4
fig. 9
2
1
3
0
4
fig. 10
cod. 3541H114 - Rev. 00 - 11/2018
Room temperature adjustment (with optional room thermostat)
Using the room thermostat, set the temperature required in the rooms. If the room ther-
mostat is not installed, the boiler will keep the system at the set system delivery setpoint
temperature.
Room temperature adjustment (with optional remote timer control)
Using the remote timer control, set the required temperature in the rooms. The boiler will
adjust the system water according to the required room temperature. For operation with
remote timer control, please refer to the relevant instruction manual.
Hot water tank exclusion (economy)
Hot water tank temperature maintaining/heating can be excluded by the user. If exclud-
ed, domestic hot water will not be delivered.
The hot water tank can be deactivated by the user (ECO mode) by pressing the ECO/
COMFORT button (detail 7 - fig. 1). In ECO mode the display activates the ECO symbol
(detail 12 - fig. 1). To activate COMFORT mode, press the ECO/COMFORT button (de-
tail 7 - fig. 1) again.
Sliding Temperature
When the optional external probe is installed, the boiler adjustment system works with
"Sliding Temperature". In this mode, the temperature of the heating system is controlled
according to the outside weather conditions, to ensure high comfort and energy saving
throughout the year. In particular, the system delivery temperature is decreased as the
outside temperature increases, according to a specific "compensation curve".
With Sliding Temperature adjustment, the temperature set with the heating buttons (de-
tail 3 - fig. 1) becomes the maximum system delivery temperature. It is advisable to set
a maximum value to allow system adjustment throughout its useful operating range.
The boiler must be adjusted at the time of installation by qualified personnel. Possible
adjustments can in any case be made by the user to improve comfort.
Compensation curve and curve offset
Press the reset button (detail 6 - fig. 1) for 5 seconds to access the "Sliding temperature"
menu; the display shows "CU" flashing.
Use the DHW buttons (detail 1 - fig. 1) to adjust the curve from 1 to 10 according to the
characteristic. By setting the curve to 0, sliding temperature adjustment is disabled.
Press the heating buttons (detail 3 - fig. 1) to access parallel curve offset; the display
shows "OF" flashing. Use the DHW buttons (detail 1 - fig. 1) to adjust the parallel curve
offset according to the characteristic (fig. 11).
Press the reset button (detail 6 - fig. 1) again for 5 seconds to exit the "Sliding Temper-
ature" menu.
If the room temperature is lower than the required value, it is advisable to set a higher
order curve and vice versa. Proceed by increasing or decreasing in steps of one and
check the result in the room.
OFFSET = 20
90
10
9
8
7
85
80
70
60
50
40
30
20
fig. 11 - Example of compensation parallel curve offset
Adjustments from Remote Timer Control
If the Remote Timer Control (optional) is connected to the boiler, the above ad-
A
justments are managed according to that given in table 1.
Table. 1
Heating temperature setting
DHW temperature adjustment
Summer/Winter Switchover
Eco/Comfort selection
Sliding Temperature
OFFSET = 40
90
10
9
8
85
6
80
5
70
4
60
3
50
2
40
1
30
20
Adjustment can be made from the Remote Timer Control menu
and the boiler control panel.
Adjustment can be made from the Remote Timer Control menu
and the boiler control panel.
Summer mode has priority over a possible Remote Timer Control
heating demand.
On disabling DHW from the Remote Timer Control menu, the
boiler selects the Economy mode. In this condition, the eco/com-
fort button (detail 7 - fig. 1) on the boiler panel is disabled.
On enabling DHW from the Remote Timer Control menu, the
boiler selects the Comfort mode. In this condition it is possible
select one of the two modes with the eco/comfort button (detail 7
- fig. 1) on the boiler panel.
Both the Remote Timer Control and the boiler card manage Slid-
ing Temperature adjustment: the boiler card Sliding Temperature
has priority.
EN
7
6
5
4
3
2
1
43

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido