2.2.5

Visual indicators

One 3-color status LED is located inside the detector window. The
statuses are as follows:
Detector status
LED color
Normal
Green
Yellow
1)
Fault, BIT
fault
Warning
Red
Alarm
Red
1)
Built-in test
For more information on the detector status, please refer to the
Technical Manual.
2.2.6

Internal tests

During normal operation, the flame detector performs the following self
tests:
Continuous feature test (performed automatically)
This test complies with SIL-2 requirements. The flame detector
continuously tests:
Input voltage level
All internal regulator voltage levels
Voltage level status of sensor and sensor circuitry for noise or
disconnection in the electronic circuitry
0-20 mA output level
Relays and heater operation
Processor watch dog
Software
Memory
Oscillator frequency
LED mode
1 Hz - flashing
Any failure is indicated by:
4 Hz - flashing
2 Hz - flashing
Steady
If the BIT was not successful, it is then automatically performed every
minute. This continues, until a successful BIT occurs and the flame
detector resumes normal operation. The fault indication remains until
power is disconnected from the flame detector. The fault indication
returns if the fault is still found when power is restored.
BIT (performed automatically every 15 minutes, but may also be
performed manually)
The BIT checks the following:
Electronics circuitry
Sensors
Window cleanliness
Fault relay:
Opens in wiring option 1, 2, and 4
Closes in wiring option 3 and 5
Status LED: Flashes yellow (4 Hz)
0-20 mA output: indicates fault (0 mA) or BIT fault (2 mA) in wiring
option 1, 2, 3
en