n PREALARM STATUS
This status indicates that an input point (detector) has
exceeded its alarm threshold. The fire control panel will
not generate an alarm until the preset prealarm- time
ends. However, if a second input point (detector in the
same SW zone) detects alarm conditions during the
Prealarm phase (and the "Double knock" option has
been programmed for that zone), the fire control panel
will generate an instant alarm.
NOTE: If the fire control panel is operating in NIGHT
mode, it will generate INSTANT ALARMS ONLY (Prea-
larm status will be bypassed automatically). If an alarm
procedure is already running, the fire control panel will
ignore prealarm conditions.
PREALARM status will also be signalled by:
Ø blinking PREALARM LEDs;
Ø on fire control panel Display;
Ø an intermittent audible signal on the fire control panel;
Ø the prealarm output points.
During the PREALARM phase you will be able to
SILENCE, INVESTIGATE or RESET the system and
view the LOG.
The Display in Figure 42 shows that fire control panel is
in PREALARM STATUS:
In this phase:
Alphanumeric keypad No function is related to
Alphanumeric keypad.
Cursor keys Use the UP Key to view the previous
event il present;
Use the DOWN Key to view the next event, if present.
Use the RIGHT Key to view the next string of data.
Use the LEFT Key to view the previous string of data.
ESC Key Use ESC key to cancel the operation and to
step back to main page.
ENTER Key The ENTER Key blocks/reactivates the
exchange between the labels of the devices and those
of the zones. When the block is enabled, the @ charac-
ter appears in the top left-hand corner of the display.
Function Key No function is related to F1 Key;
The F2 key, if the first event is caused by a device con-
nected to the control panel, takes you to the device sta-
tus page (see note*);
The F3 key, if the Last event is caused by a device con-
nected to the control panel, takes you to the device sta-
Figure 42 DISPLAY: PREALARM STATUS . N.B. If a no local control panel will generate a PREALARM, in the field
"Control panel status" the text "NETWORK PREALARM" will been shown.
First Prealarm
Prealarms Number
Control panel status
Total :0015
First
:
MS:Loop 1 det025
Last
:
MS:Loop 1 det030
#0011 :
MS:Loop 2 det034
Last Prealarm
Stored Prealarm
index
- ENGLISH - INTRODUCTION
Total
:0015
First
:
zone: R-D department
Last
:
zone: Air compressor
#0011 :
zone: Boiler room
Total
:0015
First
:
MS:Loop 1 mod012
Last
:
MS:Loop 1 mod182
#0011 :
MS:Loop 2 det034
Total
:0015
First
:
cause:
Last
:
cause: FC420CP
#0011 :
cause: FC400PH
Total
:0015
First
:
Time: 10:46:21
Last
:
Time: 10:47:18
#0011 :
Time: 10:47:12
Figure 41 Prealarm status- Scrolling Right key
tus page (see note*);
The F4 key activates the View of events stored in the
memory; if the stored event is caused by a device con-
nected to the control panel, pressing F4 again will take
you to the device status page (see note*).
From Figure 41, in the PREALARM STATUS, use the
RIGHT Key to scroll the second string of data of Prea-
larm Zones; after use the RIGHT Key to scroll the third
string of data of Prealarm causes;
RIGHT Key to scroll the fourth string of data of Prea-
larm Times and Events;
+
If the events are linked to the devices, the zone la-
bel alternates with the point label every 5 seconds.
If the zone has not been associated with the point,
only the point label will appear. In addition to the
control panel status, the time remaining until the
alarm status is activated will be displayed.
(*Note) If the event originates from a different control
panel in the network, when this key is pressed the View
LOG for the control panel which produced the event will
appear.
Prealarm Time (sec.)
This symbol shows the presence
Decreasing
of the connection between the
User Interface and the Main Board
PRE-ALARM
75
zone=078
zone=080
zone=090
This symbol
shows
the presence of following
Point identification
blocks to be scrolled by Right
cursor key,
the symbol
shows the presence
of previous blocks to be scrolled by
Left cursor key.
stat:PREALARM
n1
Push the right key to scroll
the second block of data
regarding the PREALARM zones
stat: PREALARM
zone=067
zone=456
zone=245
Push the right key to scroll
the third block of data
regarding the PREALARM causes
stat: PREALARM
Manual
Temp.
Push the right key to scroll
the fourth block of data
regarding the PREALARM times
stat: PREALARM
- 01/01/07
- 01/01/07
- 01/01/07
after use the
1° block:
39