LEGRAND WS-301 Manual Del Usuario página 2

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Walk-test feature
When the Time Delay trimpot is in the fully counterclockwise position, the sensor has a 30 second time delay. This allows you to quickly
check the sensor coverage area.
Service function
In the event of unit failure or if it is necessary to leave the load ON, remove the Service Jumper plug. This disables all automatic ON and
OFF functions and the load can only be operated using the ON/OFF button.
COVERAGE PATTERNS
The WS detects motion in areas up to 900 sq. ft. and up to 35 feet from the sensor. Ideally, the sensor is designed for small amounts of
motion in spaces up to 300 sq. ft. The Fresnel lens on the sensor is a multiple segment viewing lens with a field of view of 180°.
The sensor must have a clear view of the people in the space in order to detect occupancy. Obstructions, such as furniture blocking the
sensor's lens, may prevent occupancy detection.
Side View
Top View
MASKING THE LENS
Opaque adhesive tape is supplied so that sections of the sensor's view can be masked. This allows you to eliminate coverage in
unwanted areas. Since masking removes bands of coverage, remember to take this into account when troubleshooting coverage
problems.
Opaque tape
2

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ws-301-347

Tabla de contenido