(*2) LONWORKS Network Cable
Use the cable that is recommended by Echelon Co. and follow the instruction of the
manufacturer who produces the Upper equipment.
Cable Type and Characteristics
Cable
Belden 85102, Single/Twist pair,
Q'ty of Core 19/29, Without Shield,
150°C
Belden 8471, Single/Twist pair,
Number of Core 19/29, Without
Shield, 60°C
Level VI 22AWG, Single Core,
Without Shield
JY(St)Y2×2×0.8, 4Lines Spiral
Twist, Single Core, With Shield
TIA568A Category 5, 24AWQ,
Twist Pair
In case of using Cable with shield, connect the shield through film resistance of metal that 470kΩ,
1/4W (wattage), Degree.
4.2.
ELECTRICAL WIRING
1. Turn OFF the main power switch to the wiring that connects to HARC70-CE1 and water chiller
before electrical wiring.
2. Connect the wiring following the below Table. The number in Table indicates the refererence of
sub-chapter 4.1 "Wiring Method" (page 4/6).
Section
1 Ø 220-240V Power
Source — HARC70-CE1
Power
Line
Earthing Wire
Upper System —
HARC70-CE1
Control
Circuit
HARC70-CE1 —
Water Chillers
WIRING CONNECTION METHOD
Diameter of
Electric
Resistivity Ω/km
Wire/AWG
1.3mm/16
28
1.3mm/16
28
0.65mm/22
106
0.8mm/20.4
73
0.51mm/24
168
No
Wiring Method
AC / AC / E
AC / AC / E
LON / H-LINK
LON / H-LINK
/
4
7
Electric
Vprop%
Capacity
of Light
nF/km
Velocity
56
62
72
55
49
67
98
41
46
58
Remark
Non-polar
Non-polar