baltur COMIST 180 Manual De Instrucciones página 58

Quemadores mixtos gas
Ocultar thumbs Ver también para COMIST 180:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

INSTRUCTIONS FOR SETTING SIEMENS
SKP 15.000 E2 GAS VALVE
DESCRIPTION OF HOW THE VALVE OPERATES
Single-stage valves
W h e n t h e v a l v e r e c e i v e s t h e s i g n a l t o o p e n , t h e
p u m p c u t s i n a n d t h e m a g n e t i c v a l v e c l o s e s .
The pump transfers the oil from under the piston to above it, forcing
the piston downward, which compresses the closure return spring
with the rod and plate. The valve remains in the open position while
the pump and magnetic valve remain powered.
When the unit receives the signal to close (or if power supply is cut
off) the pump shuts down, the magnetic valve opens decompressing
the chamber above the piston. The plate is closed both by the return
spring and by gas pressure. The flow rate for this valve is calculated
to ensure full closure in less than 0.6 seconds.
This type of valve cannot regulate the gas flow rate (closure/
opening).
SKP 15...
complete with valve
1
Piston
2
Oscillating pump
3
Oil reservoir
4
Pressure chamber
5
Steam
6
Closing spring
7
Control valve
8
End switch (opitional)
20 / 36
0006080095_201207

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Comist 250Comist 300

Tabla de contenido