Controller For Charging Pump - Wolf SEM-1 Instrucciones De Montaje

Acumulador solar
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 26
Weather-dependent heating control
(heating control with integrated tank
temperature controller and tank tem-
perature sensor)
Electrical auxiliary heating
system E2 / E4,5 / E6
Electrical auxiliary heating
system
14

Controller for charging pump

Insert electronic tank temperature sensor of the heating control into the upper immersion
sleeve for tank sensors of the solar tank and attach it with sensor holder. For tanks
with sensor channel insert sensor vertically downwards until stop position is reached.
Set desired tank temperature at the tank temperature controller of the heating control.
(max. 60°C).
Electrical auxiliary heating system 2 kW/230 VAC, 4,5 kW/400 VAC, 6 kW/400 VAC
with built-in tank temperature controller and safety temperature limiter.
Screw electrical auxiliary heating system into the 1 ½" pipe coupling at the solar tank
and seal it.
The rules and regulations of the VDE and the local utilities must be observed.
The connection must be performed by a licensed electrician.
Disconnect power before opening devices.
Unscrew cap from electrical auxiliary heating system and connect system to 230VAC
or 400 VAC power supply according to included instructions. Connecting wire must be
provided on site.
SEM-1
3043754_0310

Publicidad

Tabla de contenido
loading

Tabla de contenido