Ocultar thumbs Ver también para PRS6110:

Publicidad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

Programmable Thermostats
PRS6110
PRS6320 Up to 3 Heat / 2 Cool Heat Pump
1 Specifications
Warning
Caution
• Possible electric shock or damage to equipment can occur.
• Disconnect power before beginning installation.
This thermostat requires 24 Volt AC Power or 2 properly installed "AA" Alkaline batteries for
proper operation. When connecting 24 Volt AC Power the batteries may be installed as a backup.
For use only as described in this manual. Any other use will void warranty.
1 Specifications
This thermostat is compatible with:
• Single stage heat / cool conventional and heat pump systems
• Single stage heat pumps with auxiliary heat
• Conventional systems up to 2 stages of heating and 2 stages of cooling (PRS6320 only)
• Heat pump systems up to 3 stages of heating and 2 stages of cooling (PRS6320 only)
• 250 – 750 millivolt heating only systems
• 2 or 3 wire hydronic zone systems
Electrical and control specifications:
• Electrical Rating: 24 Volt AC
• 1 amp maximum load per terminal
• AC Power: 18 – 30 Volts AC
• DC Power: 3.0 Volt DC
(2 "AA" Alkaline Batteries Included)
• Control Range: 45° – 90° F (7° – 32° C)
• Temperature Accuracy: +/- 1° F (+/- .5° C)
• Outdoor Temperature Display Range: -40° - 120° F (-40° - 49° C)
Up to 2 Heat / 1 Cool Heat Pump
or Single Stage Conventional
Up to 2 Heat / 2 Cool Conventional
Model number is located on back of thermostat.
2 Installation and Wiring
4 Installer Settings
For installation by experienced service technicians only.
Installer Manual
3 Quick Reference
5 System Testing
Terminations
• PRS6110: Rc, Rh, W1/E, C, Y1, O/B/V3, G, S2, S1
• PRS6320: Rc, Rh, W2, W1/E/W3, C, L, Y2, Y1,
O/B/V3, G, S2, S1
PRS6110-100-01

Publicidad

Tabla de contenido
loading

Resumen de contenidos para Prostat PRS6110

  • Página 1 • 2 or 3 wire hydronic zone systems Terminations Electrical and control specifications: • PRS6110: Rc, Rh, W1/E, C, Y1, O/B/V3, G, S2, S1 • Electrical Rating: 24 Volt AC • PRS6320: Rc, Rh, W2, W1/E/W3, C, L, Y2, Y1, •...
  • Página 2: Installation And Wiring

    Installation and Wiring Install your new PROSTAT thermostat in 4 basic steps: 1 Install the sub-base 3 Connect your wires 2 Provide Power 4 Attach the thermostat to the sub-base Install the Sub-Base: Provide Power • Remove the sub-base from the body of the thermostat.
  • Página 3 Connecting Your Wires (continued) Wiring Terminations for model PRS6320 Terminal Function Description Input 24 Volt AC Cooling Transformer (Dual Transformer Systems Only) Input Power Connection (24 Volt AC Heating Transformer or Millivolt Power Source) Output Fan Control W1 / E / W3 Output (W1) 1st Stage Conventional Heat, (E) Emergency Heat,...
  • Página 4 Conventional Systems Typical Wiring Configurations NOTE: The “System Type” option will be configured in the Installer Settings section. Shaded areas do not apply to the PRS6110. Heat Only or Millivolt 1 HEAT / 1 COOL Single or Dual Transformer Set System Type to 11CONV...
  • Página 5 Heat Pump Systems - Typical Wiring Configurations NOTE: The “System Type” option will be configured in the Installer Settings. Shaded areas do not apply to PRS6110. 1 HEAT / 1 COOL - No Auxiliary Heat 2 HEAT / 2 COOL - No Auxiliary Heat...
  • Página 6 Additional Wiring Options NOTE: Additional options are configured in the NOTES - Additional Wiring Options Installer Settings section. [1] These terminals can be used to connect a indoor or outdoor remote sensor. Indoor or Outdoor Remote Sensor [note 1] Attach Thermostat to Sub-Base W1/E W1/E INSTRUCTIONS...
  • Página 7: Quick Reference

    3 Quick Reference INSTRUCTIONS BACK NEXT Thermostat Reset Button ........Resets current time, program and user settings SYSTEM Button ........ Selects the system you want to control DAY/TIME Button ......Sets the current time and day of the week PROG Button ........Selects programming mode or press for 3 seconds to select SpeedSet ®...
  • Página 8: Installer Settings

    4. Press NEXT (HOLD) or BACK (PROG) to move to the next or previous setting, press RETURN to exit. BACK NEXT BACK NEXT NOTE: Shaded areas below do not apply to the PRS6110. No. Installer Setting Factory Setting Comments Default Options...
  • Página 9 No. Installer Setting Factory Setting Comments Default Options Notes follow this table) (More information follows this table) 0.5 DIF1 0.5, 1.0 or 1st Stage Differential Select a 1st stage temperature differential of 2.0 DIF1 .5°, 1° or 2° F (0.2°, 0.5° or 1.0° C) 2.0 DIF2 1.0, 2.0, 3.0, 2nd Stage Differential...
  • Página 10 No. Installer Setting Factory Setting Comments Default Options Notes follow this table) (More information follows this table) 25 Heat Set Point Upper Limit 90LIM 90-60 LIM Select a Heat Set Point Upper Limit of 90°-60° F (32°-10° C) 26 Cool Set Point Lower Limit 45LIM 45-80 LIM Select a Cool Set Point Lower Limit of 45°-80°...
  • Página 11 2nd Stage Differential [note 2] – Selects a 2nd stage temperature differential. 3rd Stage Differential [note 2] – Selects a 3rd stage temperature differential. 10 1st Stage Fan Control [note 3] – Selects a 1st stage fan control of either gas or electric heat. 11 Emergency Heat Fan Control [note 4] –...
  • Página 12 22 Auto Changeover Dead Band [note 10] – When auto changeover mode is enabled in option 5 and selected, the system automatically switches between heating and cooling when the room temperature meets the normal criteria for either a heating or cooling call. There is a forced separation (dead band) between the heating and cooling set points so that the systems do not work against each other.
  • Página 13 PROPARTS agrees to repair or replace at its option any PROSTAT thermostat under warranty provided it is returned postage prepaid to our warranty facility in a padded carton within the warranty period, with proof of the original date of purchase and a brief description of the malfunction.
  • Página 14: Termostatos Programables

    Especificaciones eléctricas y de control: Terminaciones • Capacidad eléctrica: 24 voltios CA • PRS6110: Rc, Rh, W1/E, C, Y1, O/B/V3, G, S2, S1 • Carga máxima de 1 amperio por terminal • PRS6320: Rc, Rh, W2, W1/E/W3, C, L, Y2, Y1, •...
  • Página 15: Instalación Y Cableado

    Instalación y cableado Instale el nuevo termostato PROSTAT en 4 pasos básicos: 1 Instale la sub-base 3 Conecte los cables 2 Conecte la alimentación de energía 4 Conecte el termostato a la sub-base Instale la sub-base: Conecte la alimentación de energía •...
  • Página 16: Sistemas Convencionales

    Configuraciones típicas de cableado NOTA: La opción “Tipo de sistema” será configurada en la sección Configuraciones de instalación. Zonas de sombra no se aplican a la PRS6110. Transformador doble o sencillo con 1.º etapa Calefacción solamente o milivoltios de calefacción/1.º etapa de aire acondicionado...
  • Página 17: Opciones Adicionales De Cableado

    (continuación) Configuraciones típicas de cableado NOTA: La opción “Tipo de sistema” será configurada en la sección Configuraciones de instalación. Zonas de sombra no se aplican a la PRS6110. Solo para calefacción hidrónica Transformador doble o sencillo con 2 etapas de Configure el tipo de sistema en 1HD calefacción / 2 etapas de aire acondicionado...
  • Página 18: Sistemas De Bomba De Calor

    Línea común del transformador a 24 voltios acondicionado - Incluida calefacción auxiliar de CA [nota 1] Configure el tipo de sistema en 21HP (PRS6110) Monitor opcional de falla del sistema [nota 4] Energía a 24 voltios de CA Conectado a Rh con el cable para...
  • Página 19 Configuraciones típicas de cableado NOTA: La opción “Tipo de sistema” será configurada en la sección Configuraciones de instalación. Zonas de sombra no se aplican a la PRS6110. NOTAS - Sistemas de bomba de calor 3 etapas de calefacción / 2 etapas de aire acondicionado - Incluida calefacción auxiliar...
  • Página 20: Fije El Termostato A La Sub-Base

    Fije el termostato a la sub-base W1/E W1/E INSTRUCTIONS INSTRU TRUCTI CTIONS /AUX1 /AUX /AUX /AUX1 AUX2 SYSTEM AUTO HEAT AUTO 1) Alinee el cuerpo del termostato con la sub-base. 3) Introduzca la tarjeta de consulta rápida 2) Empuje cuidadosamente el cuerpo del termostato en la ranura de la parte superior del contra la sub-base hasta que encaje en su sitio.
  • Página 21: Consulta Rápida

    3 Consulta rápida INSTRUCTIONS BACK NEXT Termostato Botón Reset (Restablecimiento) ..Reinicia la configuración de la hora actual, del programa y del usuario Botón SYSTEM (Sistema) ....Selecciona el sistema que desea controlar Botón DAY/TIME (Día/Hora) ..... Configura la hora y el día actual de la semana Botón PROG (Programar) ....
  • Página 22: Configuraciones De Instalación

    RETURN (Volver) para salir. BACK NEXT BACK NEXT NOTA: Las áreas sombreadas a continuación no aplican al modelo PRS6110. No. Configuración Valor predeter- Opciones de Comentarios de instalación* minado de fábrica configuración (Mayor información a continuación de esta tabla)
  • Página 23 90, 60, 30 o 0 segundos. residual [nota 7] oF CIRC oF CIRC 18 Bloqueo del ventilador de Deshabilita el modo de bloqueo del ventilador de recirculación on CIRC recirculación Habilita el modo de bloqueo del ventilador de recirculación * PRS6110 Solamente Manual del instalación...
  • Página 24 No. Configuración Valor predeter- Opciones de Comentarios de instalación* minado de fábrica configuración (Mayor información a continuación de esta tabla) oF REC oF REC 19 Modo de recuperación Deshabilita el modo recuperación adaptable (anticipada) on REC adaptable (ARM™) [nota 8] Habilita el modo recuperación adaptable (anticipada) I SENS I SENS 20 Control del sensor remoto...
  • Página 25 Explicación detallada de las configuraciones de instalación (consulte también las NOTAS anteriores): Perfil : Selecciona un perfil residencial (RES) o comercial (COMM). Si se selecciona un perfil residencial, están disponibles 4 eventos de programación por día. Si se selecciona un perfil comercial, está disponible la programación de 2 eventos y para 7 días.
  • Página 26 17 Retardo del ventilador de la aire acondicionado residual [nota 7] : Selecciona un retardo para el ventilador del sistema después de que el compresor de aire acondicionado se ha apagado. Este retardo ayudará a retirar el aire frío remanente de los ductos, proporcionando eficiencia adicional. Bloqueo del ventilador de recirculación: cuando está...
  • Página 27: Prueba Del Sistema

    PROSTAT. Esta garantía limitada es aplicable desde la fecha de compra original por un técnico profesional. PROSTAT acepta reparar o reemplazar a su elección cualquier termostato PROSTAT que se encuentre bajo garantía, siempre y cuando se devuelva, con gastos de correo pagados, a nuestro centro de garantías en una caja de cartón acolchada, dentro del período de la garantía, con un comprobante de la fecha original de compra y una breve descripción del defecto.

Este manual también es adecuado para:

Prs6320