MATE3 Programming
IMPORTANT:
Programming should be done by a qualified installer who is trained on programming inverter power systems. Failure to program accurate parameters for the
system could potentially cause equipment damage. Damage caused by inaccurate programming is not covered by the limited warranty for the system.
900-0132-01-00 Rev A.vsd\Page-1\2013-01-17
©2012 OutBack Power Technologies. All Rights Reserved.
Components
FLEXnet DC
HUB Communication Manager
Battery Monitor
(HUB4 or HUB10)
FW250-AC-120V-NA
Surge Protector
(Inside)
System Display and Controller
(MATE3)
Battery Status LEDs
Inverter Status LEDs
MAIN----------------
AC
MATE RTS
IN
SUM STATUS
MATE
MATE
RTS
RTS
Charge Controller
(FLEXmax 80)
Inverter/
Charger
In
23.2 V
Out 27.6 V
0.000 kW
AUX: OFF
FW250-DC-125
(175 or 250)
LED Indicators on the Inverter
Battery Status LED Indicators
Color
12 V Inverter
24 V Inverter
48 V Inverter
Green
12.5 Vdc or higher
25.0 Vdc or higher
50.0 Vdc or higher
Yellow
11.5 to 12.4 Vdc
23.0 to 24.8 Vdc
46.0 to 49.6 Vdc
Red
11.4 Vdc or lower
22.8 Vdc or lower
45.6 Vdc or lower
Inverter Status LED Indicators
Green
Inverter on (solid) or standing by (flash)
Yellow
AC source in use (solid) or standing by (flash)
Red
Inverter error or warning (see manual)
Major Components
FLEXpower System Products
Inverter/Charger
AC Conduit Box
DC Conduit Box
System Display and
Controller
3:02:14P
INV
SETUP ADV
Charge Controller
Communications
Manager
Remote Temp Sensor
FLEXnet DC Monitor
Surge Protector
Customer-Supplied Components
AC Source
Main Electrical Panel
(or overcurrent device for AC source)
Electrical Distribution Subpanel
0.0 A
0.0 A
0.0 kWH
(Load Panel)
Sleeping
Battery Bank
Photovoltaic (PV) Array
(with PV Combiner Box [PV8 or PV12])
FNDC LED Indicators
Color
Battery State-of-Charge
Green
> 90% (blinks if charge parameters are met)
≥ 80%
Yellow
≥ 70%
Yellow
≥ 60%
Yellow
Surge Protector LEDs
≥ 60% off, < 60% solid, < 50% blinks
Red
Active
Error
Phase
Contact Technical Support:
Yellow
Red
DC
Telephone: +1.360.618.4363
Yellow
Red
AC IN
Email:
Support@outbackpower.com
Yellow
Red
AC OUT
Website:
www.outbackpower.com
IMPORTANT:
Not intended for use with
life support equipment.
FX Series
VFX Series
GTFX Series
GVFX Series
GFX Series
FW250-AC-120V-NA
FW250-DC-125
FW250-DC-175
FW250-DC-250
MATE2
MATE3
FLEXmax 60
FLEXmax 80
HUB4
HUB10
RTS
FNDC
FW-SP-ACA
Utility Grid, or
AC Generator