Orbis ANRET M-90A-BUS Manual De Uso página 34

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

• Current
− Minimum reading: 0,10A
− Maximum reading: 95,0A
− Accuracy:
±0,5% full scale ± 1 digit (full scale: 90A)
− Resolution: 0,01A (range 0,10÷9,99A) or 0,1A (range 10,0÷90,0A)
• Active power
− Accuracy:
± 1% full scale ± 1 digit at 50Hz
(full scale: 100W, 1kW, 10kW, 100kW)
− Resolution: 0,1W (range 0÷99,9W) - 1W (range 100W÷999W) -
0,01kW (range 0,01kW÷9,99kW) -
0,1kW (range 10kW÷100kW)
• Reactive power
− Accuracy:
±1% full scale ± 1 digit
(full scale: 100Var, 1kVar, 10kVar, 100kVar)
− Resolution: 0,1Var (range 0÷99,9Var) - 1Var (range 100Var÷999Var) -
0,01kVar (range 0,01kVar÷9,99kVar) -
0,1kVar (range 10kVar÷100kVar)
• Active energy
− Accuracy:
class 1 to standard EN 62053-21 (I
− Resolution: 0,1 kWh
• Reactive energy
− Accuracy:
class 3 to standard EN 62053-23 (I
− Resolution: 0,1 kVarh
• Power factor (cos )
− Accuracy:
±1% ± 1 digit
− Resolution: 0,01
• Frequency
− Accuracy:
±0,1 Hz ± 1 digit (from 47 Hz a 63 Hz)
− Resolution: 0,1 Hz
b
b
- 32 -
User Manual - ANRET M-90A-BUS
=10A; I
=90A)
max
=10A; I
=90A)
max