Procedure For Measuring Diffuser, Register And Grille Velocities With Diffuser Probe; Typical Diffuser Air Flow Measuring Procedure - TSI VELOMETER 6000 Serie Manual De Uso

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

10
Procedure for Measuring Diffuser, Register and Grille
Velocities with Diffuser Probe
To calculate the air volume passing through a diffuser, register or grille
outlet, measure the velocity at the outlet, applying the air flow factor that
is provided by the outlet manufacturer, and use the following equation:
Q = K x V
Where
Q = Volume flow rate
K = Manufacturer's flow factor
V = Average measured velocity
Instructions for positioning the Diffuser Probe at the outlet for measuring
the velocity, as well as an appropriate flow factor, are available from the
outlet manufacturer. Shown below is a typical example:

Typical Diffuser Air Flow Measuring Procedure

To determine the volume of air discharged, a Velometer
with a Diffuser Probe may be used as shown below.
Note that the bottom of the positioning fins on the probe are level with
(and touching) the bottom of the intermediate spinning of the diffuser.
The probe is held vertically. The flow factors shown in the accompanying
table are applied to an average of six velocity readings taken at equally
spaced positions around the periphery of the diffuser.
English Units
Metric Units
ft
3
/min
m
3
/s
ft/min
m/s
®
Anemometer
Diffuser
Air Flow
Size
Factor
10
12
14
17
20
24
32
40
0.42
0.66
0.9
1.3
1.8
2.8
4.9
7.7

Publicidad

Tabla de contenido
loading

Tabla de contenido