5.4 Heating element

Each actuator includes a heating resistor.
As soon as the actuator is installed in the field, it is recommended
to power the resistor to prevent condensation.
Immediately put the cover back in place after start-up while
ensuring its seal is clean. Never leave actuator electrical
components without their protection cover.
In case of water intrusion:
Dry electrical components before putting back the cover.
Check electrical insulation.
6

TRAVEL LIMIT SETTINGS

The actuator is factory-set for a 90°travel.
It features 2 devices to limit the travel:
• Cams trigger switches to switch off power at an end position or
to signal a position
• Mechanical stops mechanically block rotation to protect the valve
in case of over-travel. They must not be used as travel limits.

Single cam setting

The cam rotates with the
output
shaft
triggers
a
pushing on its lever.
Cams orientation are factory
pre-set, yet you can still
re-adjust them
during the commissioning
if necessary.
Rep.
1
2
Counter-clockwise travel limit
3
4
Counter-clockwise signaling
and
switch
by
Function
Clockwise travel limit
Clockwise signaling
English
Status before installation
Pre-wired, cam pre-set
Pre-wired, cam pre-set
To wire, to set
To wire, to set
12