Cooper Greengate ControlKeeper 2 Manual De Instalación página 4

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

General Information
2.
Run a length of the digital switch LC or Belden cabling
from the GDS-I location to the low voltage section of
the ControlKeeper 2.
3.
Connect the RED wire in the cable to the +V terminal
on the back of the GDS-I and to the ControlKeeper 2 at
one of the switch input +24 VDC terminals.
4.
Connect the BLACK wire in the cable to the GND
terminal on the back of the GDS-I and to the
ControlKeeper 2 remote power connector GND
terminal.
5.
Tape back or cap the blue and white wires and shield
wire for the cable. They will not be used for connection
between the GDS-I and lighting controller.
6.
Locate the 6 foot phone style cable included in the
GDS-I box. Run this from the GDS-I into the low voltage
section of the ControlKeeper 2 enclosure plugging the
end with pin head into the GDS-I. Plug the end of the
RJ11 phone style plug into the ControlKeeper 2.
7 .
Ensure that the ControlKeeper 2 option select DIP switch
1 is in the ON position to configure the ControlKeeper
2 to accept the digital switch commands through its
communications port.
ControlKeeper 2 Panel Low-Voltage
Wire Phone Style Cable
to RJ11 Jack on CK2
and to GDS-1
Black Wire from
GDS-1 GND to
CK2 GND
Red Wire from GDS-1 V+
to CK2 +24 VDC
Cabling is Cooper Lighting
Solutions LC Cable, Belden
1502R, or Belden 1502P
Digital Switch Wiring
Network Wiring Notes:
The ControlKeeper 2 is designed to communicate with
other ControlKeeper network panels using a lighting control
RS-485 network for communications. This allows the panels
to share information back and forth as well as allows the
system to be programmed from one central location by a
computer with the Keeper Enterprise Software.
4
ControlKeeper® 2
Section
NETWORK
J51
+
-
S
U47
S1
ON
U8
CH1
+24
OFF
ON
CH2
+24
1 2 3 4
OFF
GND
U3
U4
U30
U32
U7
S5
RESET
Option Select DIP Switch 1 must be
set to ON in order for Digital Switch
Operation through the RJ-11 port
For best network performance, one of the suggested cables
should be used. If the specified cable is not used and
communications problems occur that require troubleshooting
assistance, additional charges for support may be assessed.
1.
All low voltage wiring is Class 2 wiring.
2.
All low voltage wiring must enter the cabinet into the
low voltage section of the enclosure. Low voltage
wiring can be brought from the left side of the
enclosure. Failure to separate high voltage from low
voltage wiring may cause interference with logic board
function.
3.
All low voltage wiring must be run in separate conduit
from line voltage wiring.
4.
Test all low voltage wiring for shorts to AC ground
before connection to the ControlKeeper 2 panel.
5.
If using Belden 9841 or 89841, leave all shields
disconnected making certain that shield is not exposed.
These wire types will be connected to a special
terminal block on the right side of the controller.
6.
Panels and devices on the RS-485 lighting network
should be daisy-chained. Do not create a Star or
T-tapped configuration.
S4
L1
L3
L34
L4
C80
7 .
Total network length should not exceed 4000 feet.
L5
Network Wiring:
1.
Before wiring, select the two panels that are going to
S3
be the end panels of the network and plan a wiring
scheme accordingly. Panels should be daisy-chained,
not Star or T-tapped.
2.
Pull the twisted pair wiring in conduit along the planned
route, making certain that it is separate from any high
voltage wiring.
3.
Starting at one of the end panels, connect the network
+ and - terminals to the next panel's network + and -
terminals. Continue this process through the network
making certain to observe polarity. When finished, the
two end panels will have a single pair of wires coming
into the network terminal block while all middle panels
in the network will have two sets of wires.
4.
Set the termination jumpers on the panel. If the
panel is wired as the beginning or end devicesin the
network place the termination jumper over the provided
termination pins.If the panel is not at the beginning
or end of the network, remove the jumper from the
provided termination pins.