6 - ALPIMATIC CAPACITOR BANK WIRING DIAGRAM
A – 230 & 400V NETWORK
TC client1
Secondary : 5A or 1A –Minimum power 10 VA -Class 1 (out of Alpes scope)
Disj client 1
3phase general circuit-breaker (out of Alpes scope)
F1
Fuses type aM 4A : auxiliary circuit protection
KM
Contactor coil (230-400V)
TR1
Auto transfo 400V-230V (only for network 400V)
V1,2&3
Exhausting fans is capacitor banks are equipped with detuned reactors
S1, S2
T.C Secondary connection terminals / Cables 2x2.5
G, E
Terminals for operation on GenSet (capacitor bank disconnection)
ALPIMATIC Capacitor banks - Network 230V and 400V
________________________________________________________________________________
²
(out of Alpes scope)
Page 33
_
ALPTEC 8