Descargar Imprimir esta página

Argo 245C Instrucciones De Uso página 6

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 58
WARNING! The supplied plastic conduits can be used for
wall thickness up to 50 cm; in special cases (i.e. installations
in a garret) it can be necessary to utilise longer tubes. The
maximum allowable length is 2 m. You can go to any building
material retailer, buy the plastic tube of the same diameter
(ø160 mm), of the proper length and cover it outside with
insulating material (thickness: about 3-4 cm).
EG
- Fix the suspension panel to the wall in the position indicated
on the full scale diagram.
The quantity and the type of rawl plugs (not supplied)
depends on the consistence of the wall; do not let any
space between the panel and the wall.
- Hang up the unit at the panel inserting the back fan outlet
in the grille.
- In case of an heat pump model installation it is necessary
to predispose a condensate drainage toward the outside
(a) making a hole Ø 35 mm as indicated on the full scale
diagram; if it is not possible, maintain the condensate
tube inside (b) and make a proper drainage. Assure always
a positive slope of at least 1cm/m.
- Connect the unit inserting the plug in the power socket.
- Verify the correct operation.
(b)
Plastic tubes ø 160mm
Insulation
(a)
(b)
6

Publicidad

loading

Este manual también es adecuado para:

3sc235h3hp