Self diagnosis function
■
We are constantly trying to do better service to our customers by installing such judges that show abnormality of each function as follows:
TIMER light ON
RUN light keeps flashing
RUN light ON
RUN light 2-time flash
RUN light 7-time flash
RUN light
Description of trouble
Heat exchanger sensor 1 error
1-time flash
2-time flash
Room temperature sensor error
3-time flash
Heat exchanger sensor 3 error
5-time flash
Active filter voltage error
6-time flash
Indoor fan motor error
Refrigerant is insufficient
7-time flash
Closed service valve
Heat exchanger sensor 1 error
TIMER light
Outdoor temperature sensor error
1-time flash
Outdoor heat exchanger fluid pipe
2-time flash
sensor error
Discharge pipe sensor error
4-time flash
Suction pipe sensor error
5-time flash
Current cut
1-time flash
Trouble of outdoor unit
2-time flash
Over current
3-time flash
Power transistor error
4-time flash
5-time flash
Over heat of compressor
Error of signal transmission
6-time flash
7-time flash
Outdoor fan motor error
Keep flashing
Cooling high pressure protection
Rotor lock
2-time flash
Closed service valve
1-time flash
– 29 –
Cause
• Broken heat exchanger sensor 1 wire, poor connector
connection
•
Broken room temperature sensor wire, poor connector
connection
• Broken heat exchanger sensor 3 wire, poor connector
connection
• Defective power supply
• Defective fan motor, poor connector connection
•
Refrigerant is insufficient, leaking
•
Closed serice valve
Broken heat exchanger sensor 1 wire, poor connector
•
connection
• Broken outdoor sensor wire, poor connector connection
•
Broken heat exchanger fluid pipe sensor wire, poor
connector connection
• Broken discharge pipe sensor wire, poor connector connection.
• Broken suction pipe sensor wire, poor connector connection
•
Compressor locking, open phase on compressor
output, shortcircuit on power transistor, closed service
valve
• Broken power transistor, broken compressor wire
• Broken discharge pipe sensor wire, poor connector connection
• Compressor blockage
• Overload operation, overcharge
• Broken power transistor
•
Gas shortage, defective discharge pipe sensor,
closed service valve
•
Defective power supply, Broken signal wire, defective
in/outdoor unit boards
• Defective fan motor, poor connector connection
• Gas over charge, short circuit of outdoor unit
• Defective compressor
• Open phase on compressor
• Defective outdoor unit boards
• Closed serice valve