4.2- Language
Defines the language of the logger menus.
Allows you to change the language of the menus and texts in general displayed on the screen.
Select the language and press SET.
4.3- Input wizard
Configures the logger inputs.
Select the input to be configured and press SET.
This wizard will help you to configure each input. The parameters available will vary depending on the type of input
configured.
Use the N, Q, P and O keys to change the values and the SET key to confirm them and go on to the next
parameter. To go back to the previous option, press ESC.
Input type:
Select the input type in function of the element connected to it and press SET to confirm.
Disabled: There is no element connected to it (on
confirming, the wizard will appear).
NTC: There is an NTC probe connected.
Pt100: There is a Pt100 probe connected (only
AKO-1575x and AKO-1578x)
Display unit:
(Only for NTC, Pt100, Pt1000 and 4-20mA)
Define the display units (ºC or ºF). If the input type is 4-20mA, you can define the units by means of the built-
in text editor (see page 28).
Description:
Allows you to enter a name of up to 10 characters to describe the input (Camera 1, Fruits, Ext. probe, etc.),
using the built-in text editor (see page 28).
Enable max. alarm:
(Only for NTC, Pt100, Pt1000 and 4-20mA)
Allows you to enable the maximum value reached alarm. (If you select "Disable", on confirming, the wizard
will go to the "Enable min. alarm" parameter).
Maximum alarm:
(Only for NTC, Pt100, Pt1000 and 4-20mA)
Defines the maximum value from which the alarm will be activated.
Pt1000: There is a Pt1000 probe connected.
4-20mA: There is a 4-20mA converter connected.
Digital: There is a voltage-free contact connected.