5. Installing the grille
A
B
D
B
D
A
Fig. 5-9
C
A
B
A Screw (4 × 8) 5
B Corner panel
C Safety wire
Fig. 5-10
6. Test run (Fig. 6-1)
CENTRALLY CONTROLLED
CHECK
˚C
STAND BY
DEFROST
TEMP.
2
TIMER SET
PAR-20MAA
Fig. 6-1
A
Fig. 6-2
C
A Button
B Vane motor
C Up/down vanes
D Connector
G
D
H
BC
D
1Hr.
ON OFF
˚C
CLOCK
FILTER
CHECK MODE
E
TEST RUN
ERROR CODE
FUNCTION
NOT AVAILABLE
A
ON/OFF
5
FILTER
CHECK TEST
1
3
4
B
A Insert the pump end 3 to 5 cm
C
B Cover of water supply inlet
C About 1000 cc
D
D Water
E Drain plug
E
5.5. Locking the up/down airflow direction (Fig. 5-9)
The vanes of the unit can be set and locked in up or down orientations depending
upon the environment of use.
• Set according to the preference of the customer.
The operation of the fixed up/down vanes and all automatic controls cannot be
performed using the remote controller. In addition, the actual position of the vanes
may differ from the position indicated on the remote controller.
1 Turn off the main power switch.
Injuries and or an electrical shock may occur while the fan of the unit is rotating.
2 Disconnect the connector for the vane motor of the vent that you want to lock.
(While pressing the button, remove the connector in the direction indicated by the
arrow as shown in the diagram.) After removing the connector, insulate it with
tape.
5.6. Check
• Make sure that there is no gap between the unit and the grille, or between the grille
and the surface of the ceiling. If there is any gap between the unit and the grille, or
between the grille and the surface of the ceiling, it may cause dew to collect.
• Make sure that the wires have been securely connected.
5.7. Installing the intake grille (Fig. 5-10)
Note:
E
When reinstalling the corner panels (each with a safety wire attached), connect
the other end of each safety wire to the grille using a screw (4 pcs,
4 × × × × × 8) as shown in the illustration.
* If the corner panels are not attached, they may fall off while the unit is operating.
• Perform the procedure that is described in "5.2. Preparing to attach the grille" in
reverse order to install the intake grille and the corner panel.
• Multiple units can be installed with grille so that the position of the logo on each
corner panel is consistent with the other units regardless of the orientation of the
intake grille. Align the logo on the panel according to the wishes of the customer as
shown in the diagram to the left. (The position of the grille can be changed.)
D Refrigerant piping of the main unit
F
E Drain piping of the main unit
F Position of the corner panel when sent from the factory (logo attached).
* Installation in any position is possible.
G Position of the levers on the intake grille when sent from the factory.
* Although the clips can be installed in any of four positions, the configuration shown here is
recommended.
(It is not necessary to remove the intake grille when maintenance is performed on the elec-
tric component box of the main unit.)
H Receiver (Only PLP-6AALM Panel)
1 Press [TEST RUN] button twice → displaying [TEST RUN] on the screen.
2 Press [Selecting operation] button. → Check that wind is blowing out.
3 Press [Fan speed adjustment] button. → Check that the wind speed is changed.
4 Press [Up/down airflow selection] button to change wind direction.
5 Press [ON/OFF] button to clear test run. → Test run stops.
A Lighting in operation
B Displaying inspection code
C Displaying remaining test run time
D Displaying indoor unit's liquid pipe temperature
E Displaying test run
Note:
• The 2-hour-set timer is activated to automatically stop test run after two hours.
• The remote controller displays the temperature of the indoor unit's liquid
pipe on the temperature display section during test run.
6.1. Check of drainage (Fig. 6-2)
• During the trial run, ensure the water is being properly drained out and that no
water is leaking from joints.
• Always check this during installation even if the unit is not required to provide cool-
ing/drying at that time.
• Similarly, check the drainage before finishing ceiling installation in a new premises.
(1) Remove the cover of the water supply inlet and add about 1000 cc of water using
a water supply pump etc. During this process, be careful not to spray water into
the drain pump mechanism.
(2) Confirm that water is being drained out through the drainage outlet, after switch-
ing over from remote control mode to trial run mode.
(3) After checking the drainage, ensure that the cover is replaced and the power
supply is isolated.
(4) After confirming the drainage system is functioning, replace the drain plug.
9