RS-232 Communications Protocol & Command Set
SWITCH OUTLET BANK
Turns a specific outlet bank on or off. Switching is immediate
with no delay.
Send to UPS:
Example: !SWITCH 2 ON<CR> (turns on outlet bank 2)
_________________________________________
If power to bank 1 is switched:
Action:
Response from UPS:
_________________________________________
If power to bank 2 is switched AND battery level > Shutoff Threshold:
Action:
Response from UPS:
_________________________________________
If UPS battery level > Shutoff Threshold
Action:
Response from UPS:
_________________________________________
If UPS battery level < Shutoff Threshold
Action:
Response from UPS:
_________________________________________
If power button is OFF and state is changed to ON
Action:
Response from UPS:
_________________________________________
If entered bank or state are invalid
Response from UPS:
!SWITCH bank state<CR>
bank = {1, 2}
state = {ON, OFF}
Switch power to Outlet Bank 1
$BANK 1 = state<CR>
Switch power to Outlet Bank 2
$BANK 2 = state<CR>
Turn on Outlet Bank 2
$BANK 2 = ON<CR>
Turn off Outlet Bank 2
$BANK 2 = OFF<CR>
$BATTERY = charge%<CR>
Activate Power Button
$BUTTON = ON<CR>
$INVALID_PARAMETER<CR>
SET BANK 2 THRESHOLD
Sets the battery level threshold in which Outlet Bank 2 shuts off.
Send to UPS:
level is a number between 20 and 100 represents the bat-
tery charge level where Outlet Bank 2 is shut off to the reserve
remaining battery charge for the equipment connected to Outlet
Bank 1. level shall be rounded up to the nearest interval of 10.
If level is >19 AND level <101
Action:
Response from UPS:
_________________________________________
If specified level is invalid
Action:
Response from UPS:
_________________________________________
SET BUZZER MODE
With Buzzer Mode ON, the buzzer will sound during UPS Mode.
Send to UPS:
_________________________________________
If specified mode is invalid
Action:
Response from UPS:
_________________________________________
9
!SET_BATTHRESH level<CR>
SHUTOFF THRESHOLD will be set
to a value between 20 and 100
$BTHRESH = level<CR>
No action will be taken
$INVALID_PARAMETER<CR>
!SET_BUZZER mode<CR>
mode = {ON, OFF}
No action will be taken, UPS will
request a valid mode setting
$INVALID_PARAMETER<CR>
$BUZZER = mode<CR>