9. CONFIGURATION.
In the configuration menu we can adjust either maximum current (A) and minimum pump speed (FL). Next steps shoud be followed:
1. Press push-button MENU during 3 seconds to start the configuration sequence.
2. Input the nominal intensity value in Amps using
For Easy 09MM must be within 0 and 9 A, the default value is 9 A.
For Easy 12MM must be within 0 and 12 A, the default value is 12 A.
For Easy 06MT must be within 0 and 6 A, the default value is 6 A.
For Easy 10MT must be within 0 and 10 A, the default value is 10 A.
This value is located over the characteristics plate of the motor. Press ENTER for validation.
3. Using the START/STOP pushbutton verify the rotation sense. By mean of keys pq(0/1) we can change it. Press
ENTER for validation. MT types only.
p
4. Using
can be increased the lower limit of the speed of rotation.
The value must be within 30 and 35 Hz. Default value is 30 Hz.
Press push-button ENTER, for validation and quit this menu.
5. If the installation does not have level probe press ENTER to validate 0.
If the installation has a level probe, use keys pqto change 0 by 1.
6. System is ready. By mean of AUTO ON/OFF quit the manual operating mode.
EGISTER OF OPERATION DATA AND ALARMS.
10. R
By using simultaneously MENU +
of ENTER we can advance through the sequence, once finished the sequence we come back to the main display . This is all
the sequence:
REGISTER HOURS (HF). Counter of total time that the pump has been operating.
n
REGISTER STARTS (CF). Number of cycles of operation, a cycle is a start and a stop.
n
REGISTER SWITCH (Cr). Number of connections to the electric supply.
n
ALARM COUNT DRY RUN (A1). Number of dry-running alarms.
n
ALARM COUNT I MAX (A2). Number of overcurrent alarms.
n
ALARM COUNT. DISCONNECTED PUMP (A3). Number of disconnected pump alarms.
n
ALARM COUNT. TEMP (A6). Number of alarms by excessive temperature.
n
ALARM COUNT. SHORTCIRCUIT (A7). Number of short circuit alarms.
n
ALARM COUNT. OVERVOLTAGE (A8). Number of overvoltage alarms.
n
ALARM COUNT. UNDERVOLTAGE (A9). Number of undervoltage alarms.
n
All the records are saved even if the device has been disconnected from the electric supply.
Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For example, to
indicate 10234 overcurrent alarms:
.....
11.
"CE" STAMENT OF COMPLIANCE.
COELBO CONTROL SYSTEM, S.L. We state, on our's own responsibility, thal all materials herewith related comply with the
following European standards:
Product's name/Type: SPEEDMATIC EASY 09 MM / 12 MM / 06 MT / 10 MT
As per the European Standards:
UNE EN 60730-1:1998+A11:1998+A2:1998+A14:1998+A15:1998+A20:1998+A17:2001+ERRATUM A1:2001+A18:2003
UNE EN 60730-2-6:1997+A1:1998+A2:1999+CORR A1:2001+CORR A2:01
UNE EN 61800-3 Class C1 or Class C2 depending on model
pq
during 3" is acceded to REGISTER OF OPERATION DATA AND ALARMS, by mean
p
2006/95/EC Low Voltage Directive on Electrical Safety
2004/108/CE Electromagnetic Compatibility.
2002/95/CE RoHS Directive
enabling the thermal protection.
-10-
ON
OFF
....
F. Roldán Cazorla
Tehnical director