Operation And Installation - Flotec FPSE 2800A Serie Manual Del Usuario

Bombas sumergibles para el manejo de líquidos con sólidos
Ocultar thumbs Ver también para FPSE 2800A Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation / Electrical / Operation / Service
Use a 2" (5.1 cm) swing check valve in pump discharge
to prevent backflow of liquid into sump basin. Check
valve should be a free flow valve that will easily pass
solids.
NOTICE: For best performance of check valve when
handling solids, do not install it with discharge angled
more than 45° above the horizontal. Do not install check
valve in a vertical position as solids may settle in valve
and prevent opening on startup.
Drill a 3/16" (4.7mm) hole in discharge pipe about 1"-2"
(2.5 - 5.1cm) above pump discharge connection (but
below check valve) to prevent airlocking the pump.
ELECTRICAL
Hazardous voltage. Can shock, burn, or
cause death. When installing, operating, or servicing this
pump, follow safety instructions listed below.
Step 1. DO NOT splice the electrical power cord.
Step 2. DO NOT allow electrical cord plug to be sub-
merged.
Step 3. DO NOT use extension cords. They are a fire
hazard and can reduce voltage sufficiently to pre-
vent pumping and/or damage motor.
Step 4. DO NOT handle or service pump while it is con-
nected to power supply.
Step 5. DO NOT remove grounding prong from plug or
modify plug.To protect against electrical shock,
the power cord is a three-wire conductor and
includes a 3-prong grounded plug. Plug pump
into a 3-wire, grounded, grounding-type recepta-
cle. Connect pump according to electrical codes
that apply.
For automatic operation, plug or wire pump into an
automatic float switch or pump controller. Pump will run
continuously when plugged directly into an electrical
outlet. Connect or wire pump to an individual branch
circuit with no other outlets or equipment in the circuit.
Size fuses or circuit breakers according to chart below.
FUSE DATA
FPSE
Model
2800A
3200A
For parts or assistance, call Flotec Customer Service at
HP
Voltage
1/3
115
4/10
115
Risk of electrical shock and fire. Be sure
that power supply information (Voltage/ Hertz/Phase)
on pump motor nameplate matches incoming power
supply exactly. Install pump according to all electrical
codes that apply.

OPERATION AND INSTALLATION

NOTICE: Do not allow pump to run in a dry sump. It
will void the warranty and may damage the pump.
An automatic overload protector in the motor will pro-
tect motor from burning out due to overheating/overload-
ing. When motor cools down, overload protector will
automatically reset and start motor.
If overload trips frequently, check for cause. It could be a
stuck impeller, wrong/low voltage, or electrical failure in
motor. If an electrical failure in the motor is suspected,
have it serviced by a competent repairman.
Pump is permanently lubricated. No oiling or greasing is
required.
GENERAL
Hazardous voltage. Can shock, burn, or
cause death. Before removing pump from basin for ser-
vice, always disconnect electrical power to pump and
control switch.
Risk of electrical shock. Can burn or kill.
Do not lift pump by ower cord. See "Cord Lift Warning"
on Page 5.
Submerge pump in a disinfectant solution (chlorox or
chlorine) for at least one hour before disassembling
pump.
The pump motor contains a special lubricating oil which
should be kept clean and free of water at all times.
Individual Branch Circuit
Required (Amps)
15
15
1-800-365-6832
3
Dual Element Time
Delay Fuse Amps
10
10

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Fpse 3200a serie

Tabla de contenido