4. Specifications and intended use

4. Specifications and intended use
Version
CE-conformity:
Product Safety : 2001/95/EG Product Safety
EMC:
Product Safety : EN 607301: 2002
Supply voltage
DC 15 ... 24 V / AC 24 V ±10 %
Scale range / measuring range
Humidity:
0 % ... 100 % rF
Temperature: -20 °C ... +80 °C
Power consumption
0.5 W / 1.7 VA
Transmitter output
Humidity:
DC 0 ... 10 V, load: min. 5 kOhm
Temperature: DC 0 ... 10 V, load: min. 5 kOhm
Accuracy
Humidity:
±3 % between 20 % ... 80 % rF
Temperature: ±1 % between 5 ... 45 °C
Operating temperature
Ambient:
-20 °C ... +70 °C
Sensor tip:
max. 60 °C

Ingress protection

IP 65 per EN 60529 / lEC 529 (connection head)
WIKA operating instructions air2guide model A2G-70
2004/108/EG Electromagnetic compatibility
EN 607301: 2002