3 INSTALLATION AND CONNECTION

3.1 CONNECTIONS
Description
Power supply
Controlled voltage
Digital inputs
Relay outputs

CONNECTION INSTRUCTIONS

The electrical connection of the safety relay for other devices is carried out by fixed terminals with screws. To
ensure the electrical connections integrity the following connection instructions must be considered:
ATTENTION!
Ensure that safety relay is turned off before perform the electrical connections.
Do not use the safety relay like supply to external devices.
Table 3.1: Connection descriptions
Type
Pin
Function
IN
A1
AC / DC Positive [+]
IN
A2
AC / DC Negative [-]
OUT
S10
Negative reference [-]
OUT
S11
Positive reference [+]
IN
S12
Channel 1 PNP Input
S13
Channel 2 NPN Input
IN
S14
Channel 2 PNP Input
IN
S21
PNP Start Control
13-14
Output Current paths
OUT
23-24
3 NO contacts
33-34
Auxiliary Output
OUT
41- 42
1 NC contact
Table 3.2: Electrical connection instructions
Parameter
Cable section
Cable resistance
Cable length of control line
Connection type
Screw terminals
Tool
Screwdriver slot Nº3
Torque
Installation and Connection
Front View
41
13
23
A1
S11
S14
RELAY 1
RELAY 2
S10
S12
S13
42
14
Value
24 to 12 AWG
0.5 to 2.5 mm²
≤ 40 Ω
≤ 100 m
≤ 0.4 N.m.
33
S21
A2
24
34
CPW22 | 11