Gas Connection; Electrical Connections; Service And Maintenance; Air/Fume Ducts - Ferroli DOMItech C 24 D Instrucciones De Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 11

3.4 Gas connection

The gas must be connected to the relevant union (see figure on cover) in conformity with
the current regulations, with a rigid metal pipe or with a continuous surface flexible s/steel
tube, installing a gas cock between the system and boiler. Make sure all the gas connec-
tions are tight.

3.5 Electrical connections

Important
B
The unit must be connected to an efficient earthing system in conformity with
current safety regulations. Have the efficiency and suitability of the earthing
system checked by professionally qualified personnel; the Manufacturer de-
clines any liability for damage caused by failure to earth the system.
The boiler is prewired and provided with a "Y" type cable (without plug) for con-
nection to the electric line. The connections to the power supply must be per-
manent and equipped with a double-pole switch with contact opening distance
of at least 3 mm, installing fuses of max. 3A between the boiler and the line.
Make sure to respect the polarities (LINE: brown wire / NEUTRAL: blue wire /
EARTH: yellow/green wire) in connections to the electric line.
B
The unit's power cable must not be replaced by the user; if damaged, switch
the unit off and have the cable replaced by professionally qualified personnel.
If replacing the power cable, only use "HAR H05 VV-F" 3x0.75 mm2 cable with
max. ext. diameter of 8 mm.
Room thermostat (optional)
B
IMPORTANT: THE ROOM THERMOSTAT MUST HAVE VOLTAGE-FREE
CONTACTS. CONNECTING 230 V TO THE ROOM THERMOSTAT TERMI-
NALS WILL PERMANENTLY DAMAGE THE ELECTRONIC BOARD.
When connecting time controls or a timer, do not take the power supply for
these devices from their breaking contacts Their power supply must be by
means of direct connection from the mains or with batteries, depending on the
kind of device.
Accessing the electrical terminal block
The electrical terminal block can be accessed after removing the casing. The layout of
the terminals for the various connections is also given in the wiring diagram in fig. 21.
72
139
fig. 8 - Accessing the terminal block

3.6 Air/fume ducts

The diameter of the flue connection pipe must not be less than that of the connection on
the anti-backflow device. Starting from the anti-backflow device it must have a vertical
section at least 50 cm long. Current standards must be complied with regarding sizing
and installation of the flues and connection pipe.
B
The boiler is also equipped with a safety device (fume thermostat) that stops
operation of unit in case of inadequate draught of obstruction of the flue. This
device must never be tampered with or deactivated.
30
EN

4. SERVICE AND MAINTENANCE

4.1 Adjustments
Gas conversion
The unit can operate on natural gas or LPG and is factory-set for use with one of these
two gases, as clearly shown on the packing and on the dataplate. Whenever a gas dif-
ferent from that for which the unit is arranged has to be used, the special conversion kit
will be required, proceeding as follows:
1.
Replace the nozzles at the main burner, fitting the nozzles specified in the technical
data table in cap. 5, according to the type of gas used
2.
Modify the parameter for the type of gas:
3.
Adjust the minimum and maximum pressures at the burner (ref. relevant para-
graph), setting the values given in the technical data table for the type of gas used
4.
Apply the sticker contained in the conversion kit, near the dataplate as proof of the
conversion.
TEST mode activation
Press the heating buttons (details 3 and 4 - fig. 1) together for 5 seconds to activate the
TEST mode. The boiler lights at the maximum heating power set as described in the fol-
lowing section.
The heating and DHW symbols (fig. 9) flash on the display; the heating power will be dis-
played alongside.
138
Press the heating buttons (details 3 and 4 - fig. 1) to increase or decrease the power
(min.=0%, max.=100%).
Press the DHW button "-" (detail 1 - fig. 1) and boiler power is immediately adjusted to
min. (0%). Press the DHW button "+" (detail 2 - fig. 1) and boiler power is immediately
adjusted to max. (100%).
If the TEST mode is activated and enough hot water is drawn to activate the DHW mode,
the boiler remains in TEST mode but the 3-way valve goes to DHW.
3
4
To deactivate the TEST mode, press the heating buttons (details 3 and 4 - fig. 1) for 5
seconds.
The TEST mode is automatically disabled in any case after 15 minutes or on stopping of
hot water drawing (if enough hot water is drawn to activate the DHW mode).
Pressure adjustment at the burner
Since this unit has flame modulation, there are two fixed pressure settings: minimum and
maximum, which must be those given in the technical data table according to the type of
gas.
Connect a suitable pressure gauge to the pressure point "B" downstream of the
gas valve.
Activate the TEST mode (see cap. 4.1).
Press the Eco/Comfort button for 2 seconds to access the gas valve Calibration
mode.
The card goes to the setting "q02"; displaying the actually saved value, by pressing
the DHW buttons .
If the pressure gauge reading is different from the nominal maximum pressure, pro-
ceed by increases/decreases of 1 or 2 units of parameter "q02" by pressing the
DHW buttons : the value is stored after each modification; wait 10 seconds for the
pressure to stabilise.
Press the heating button "-" (ref. 3 - fig. 1).
The card goes to the setting "q01"; displaying the actually saved value, by pressing
the DHW buttons .
If the pressure gauge reading is different from the nominal minimum pressure, pro-
ceed by increases/decreases of 1 or 2 units of parameter "q01" by pressing the
DHW buttons : the value is stored after each modification; wait 10 seconds for the
pressure to stabilise.
Recheck both adjustments by pressing the heating buttons and adjust them if nec-
essary by repeating the above procedure.
Press the Eco/Comfort button for 2 seconds to return to the TEST mode.
Deactivate the TEST mode (see cap. 4.1).
Disconnect the pressure gauge.
cod. 3540Z952 - Rev. 00 - ediz. 10/2013
DOMItech C 24 - 32 D
put the boiler in standby mode
press the DHW buttons details 1 and 2 - fig. 1 for 10 seconds: the display shows
"b01" blinking.
Press the DHW buttons fig. 1 (details 1 and 2 - ) to set parameter 00 (for nat-
ural gas operation) or 01 (for LPG operation).
press the DHW buttons details 1 and 2 - fig. 1 for 10 seconds.
the boiler will return to standby mode
fig. 9 - TEST mode (heating power = 100%)
eco
comfort
reset

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Domitech c 32 d

Tabla de contenido