KNX/EIB
SWITCH ACTUATOR
IT KNT 004 / IT KNT 012
INSTRUCTIONS MANUAL
Technical specifications
Operation voltage
Current consumption (mA)
Power consumption (W)
Number of contacts
Contact
Rated voltage
Rated current
Power loss at max. load
Max. load / cycles
100.000 cycles:
Incandescent lamp
230V Halogen lamp
LV Halogen lamp with Transformer
Fluorescent lamp Not Compensated
Fluorescent lamp Compensated
650W (70uF)
CFL lamp
Operation period per output
Delay time after ON
Delay time after OFF
EIB/KNX
Load output
Mounting
IT KNT 004: 4 modules wide
Dimensions
IT KNT 012: 12 modules wide
Weight
IP grade
Security class
Operation temperature
Storage temperature
Transport temperature
Humidity
Description
Modular switch actuators with 4 or 12 output channels for EIB/KNX Bus installations.
Programming and commissioning by ETS3 or later.
It is able to switch 4 or 12 independent electrical AC loads or three-phase loads by the switch actuators with maximum
output of 16A per output and manual switch, as well as visible switching status.
There are same following programming functions for each output:
· Time function: on/off delay
· Staircase function with the warning and adjustable staircase lighting time
· Scene, preset control: 8bit/1bit
· Logic operation: AND, OR, XOR, gate function
· Status response
· Forced operation and safe function
· Threshold function setup
· Control of electro thermal valve function
· Selection of preferred status after bus voltage failure and recovery
21V
~ 30V
(via Bus)
DC
DC
< 12mA
Max. 360mW
1 - Label carrier
2 - Programming key
IT KNT 004: 4 Channels
3 - Red LED: Entering physical address
IT KNT 012: 12 Channels
Free-voltage
250V~ (50/60Hz)
Dimensions
16A
- IT KNT 004:
IT KNT 004: 2W
IT KNT 012: 8W
30.000 cycles:
1250W
2500W
1200W
2500W
500VA
500VA
1200W
2500W
1300W (140uF)
560W
1100W
55ms
30ms
25ms
- IT KNT 012:
Bus terminal
Screw terminal
DIN-rail 35mm
IT KNT 004: 300g
IT KNT 012: 700g
IP20, EN60529
Class II, EN61140
-5ºC ~ +45ºC
-25ºC ~ +55ºC
-25ºC ~ +70ºC
< 93%
6
5
A
B
C
D
1
IT KNT 004
A
B
C
D
I
I
I
I
0
0
0
0
2
16A x 4 unit 250V~
3
- +
4
4 - EIB/KNX Bus terminal
5 - Manual operation
6 - Load terminal
Green LED: Normal operation
70,5mm
60mm
A
B
C
D
IT KNT 004
A
B
C
D
I
I
I
I
0
0
0
0
16A x 4 unit 250V~
- +
143mm
A
B
C
D
E
F
G
H
I
J
K
L
A
B
C
D
E
F
G
H
I
J
K
L
I
I
I
I
I
I
I
I
I
I
I
I
0
0
0
0
0
0
0
0
0
0
0
0
16A x 12 unit 250V~
- +
Installation
- IT KNT 004:
L1
L2
L3
N
- IT KNT 012:
L1
L2
L3
N
A
B
C
A
B
C
I
I
0
0
Important information
· Installation and commissioning of the device may only be carried out by quealified personnals. The relevant standards,
60mm
directives, regulations and instructions must be observed when planning and implementing the electric installation.
· Protect the device against moisture, dirt and damage during transport, storage and operation.
· Do not operate the device outside the specified technical data (e.g. temperature range).
· The device may only be operated in closed enclosures (e.g. distribution boards).
A
B
C
D
IT KNT 004
A
B
C
D
I
I
I
I
0
0
0
0
16A x 4 unit 250V~
- +
Bus KNX
D
E
F
G
H
I
J
K
L
D
E
F
G
H
I
J
K
L
I
I
I
I
I
I
I
I
I
I
0
0
0
0
0
0
0
0
0
0
16A x 12 unit 250V~
- +
Bus KNX