Descargar Imprimir esta página

Aventics RMV AS-i Instrucciones De Servicio página 3

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

English
1
Safety notes
W
The bus coupler is to be used exclusively in bus systems according to AS-i
specifications.
W
This is a class A product. In a living environment this product can cause
radio interference, in which case it may be necessary for the user to take
appropriate measures.
W
Installation should only be done by trained specialists.
W
Only operate the bus coupler in a completely assembled state. Always
turn off the power when plugging and unplugging the plug connectors.
W
The power supply must be installed in such a way that no surge voltages
can occur on the output side.
W
The bus coupler has an integrated watchdog function, which resets the
outputs in the event of a bus communication failure.
2
Addressing the bus coupler
Connect the plug (7) to the programming device using an addressing cable.
Assign an address from 1 to 31 and document it on the label (6), (10).
The bus coupler address set at the factory is: 0
3
Connecting the bus cable
Connect the yellow profile cable (9) to the plug (7) via the cable socket (8).
Status-LED (4) and (5):
POWER
FAULT
off
off
green
off
green
red
4
Triggering the valves
The valves are triggered by the bus coupler's (3) 4 outputs according to the
following allocation scheme.
Data bit
Valve location
1
2
D0
solenoid 14
D1
solenoid 14
D2
solenoid 12
D3
solenoid 12
Meaning
No supplyvoltage present at bus
Cyclic I/O data traffic
No I/O data traffic
3
4
solenoid 14
solenoid 14
AVENTICS | RMV AS-i | 1987765505–BDL–001–AB
5
Technical data
Characteristics
General
Degree of protection
IP 65 (EN 60529/IEC 529) when assembled.
Ambient temperature
0°C to +50°C
Bus coupler
Rated voltage
according to AS-i specifications 26,5 V ... 31,6 V
Power consumption
40 mA
Current per
50 mA
valve solenoid
I/O-Code
8
ID-Code
F
ID2-Code
E
Electromagnetic compatibility
Interference signal/
EN 50295
Interference immunity
Accessories (order separately)
cable socket
1 824 484 064
(1 piece) incl. label
Addressing cable
on request
6
Figure legend
1 Master
2 Power supply
3 Bus coupler
4 LED POWER (supply, green)
5 LED FAULT (status, red)
6 Identification field
7 Plug bus connection (PWR)
8 Cable socket bus connection
9 Yellow profile cable
10 Label
3

Publicidad

loading

Este manual también es adecuado para:

1987765505