Current Limiting Data according to UL 489
Circuit Breaker
Max. Frame
Type
Size A
NZM10H
600
Instructions for Field Wiring
Terminal Kit System for NZM 10 (C)NA and NZM 10 N/B-NA
Circuit Breaker
Bolt-on
Terminal Cover (3) 2Z1213-651.28 L1; L2; L3
K2x240W-NZM 10
K2x240IP-NZM 10
Terminal Cover (3) 2Z123-651.28
Insulating Plate (1) 4Z 123-651.1003
Auxiliary Terminal
K2x120-NZM 10
Auxiliary Terminal
K300-NZM 10
Auxiliary Terminal
Moeller GmbH,Industrieautomation, 53105 Bonn
For Immediate Delivery call KMParts.com at (866) 595-9616
' 2002 by Moeller GmbH
Threshold Current
MAXIMUM
RMS
2
Peak
I
dt
SYM
3
2
kA
10
A
s
kA
34.0
2800
39
42.0
5500
39
39
40.0
5500
Wire Size
2xAWG2-2x500MCM
AWG 18-14
2xAWG3/0-2x250MCM
AWG 18-14
250MCM-500MCM
AWG 18-14
Intermediate Current
MAXIMUM
RMS
2
Peak
I
dt
SYM
3
2
kA
10
A
s
kA
125
50.0
3500
65
52.0
6600
42
45.0
7200
Cu + Al
Cu only
Cu only
High Interrupting Capacity
MAXIMUM
RMS
2
Peak
I
dt
SYM
3
2
kA
10
A
s
kA
200
55.0
4000
100
61.0
8000
50
48.0
8000
Max. A-Rating
TighteningTorque
600 A
600 A
500 A
350 A
nderungen
11/95 AWA123-1089
vorbehalten
Printed in the Federal Republic of Germany (02/02)
Frequency
60 Hz
Voltage (V)
240
480
600
50 Nm
50 Nm
1,2 Nm
8 Nm
1,2 Nm
8 Nm
1,2 Nm
11/11
10004851/0013 FD