EN
Rated voltage
Cooling capacity (with pump)
Flow rate (pump)
Pump pressure
Ambient temperature
Target value tolerance
Refrigerant
Max power consumption
Max current consumption
Starting current
Control voltage
Airflow external
Tank volume
Connections (medium)
Sound pressure 1m @ 50 Hz (EN ISO
3741)
Weight (without packaging)
E-box degree of protection EN 60529
Colour
Operating and Maintenance Instructions - Chiller - Series EB 210 - EB 440
EB 410 WT B
400 / 3 / 50
460 / 3 / 60
(1)
40.5 / 48.5
105 / 125
2.5
+15 ... +43
±2
R407C
18.1 / 21.8
31.5 / 33
131.1 / 134.5
24 AC
12,000
200
1 ½"
72
476
IP54
RAL7035
EB 440 WT B
400 / 3 / 50
460 / 3 / 60
43.5 / 52.2
101 / 125
2.5
+15 ... +43
±2
R407C
19.1 / 23
34.5 / 35
142.9 / 146.6
24 AC
12,000
200
1 ½"
74
500
IP54
RAL7035
© Pfannenberg GmbH
Unit
V / ~ / Hz
kW
l/min
bar
°C
K
kW
A
A
V
m³/h
l
BSP
dB(A)
kg
Page 66 / 293