Chapter 4 Installation; Mounting A Prcab Cabinet; Control Panel Wiring - INIM Electronics PREVIDIA216 Manual De Instalación

Ocultar thumbs Ver también para PREVIDIA216:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 45
Installation
Note:
Installation of these fire detection panels must be carried out in full respect of the local fire codes, laws
and bylaws in force, and in accordance with the instructions and guidelines herein.
The control panel must be mounted in a place that is:
• Dry
• Far from electromagnetic interference (electrical equipment, heating units, air-conditioning units, radio transmitters,
etc.)
The mounting location must satisfy all the requirements of the respective Fire Code, laws and bylaws in force.
The system must be installed in accordance with the following procedure:
1.
Lay the cables
2. Connect all the devices to the BUS, loop and in the protected area
3. Install system peripherals
4. Mount the control panel to the wall
5. Install accessory modules
6. Power up the system
7.
Test the system
4.1

Mounting a PRCAB cabinet

1.
Remove the securing screws and door (paragraph 3.1 - [D]).
2. Remove the front-plate grounding conductor (paragraph 3.1 - [C]) and, if present, the CAN wire.
3. Push the hinge grips, located at the top and bottom of the door hinges, inwards (paragraph 3.1 - [E]) to release the
cabinet front plate.
4. Remove the seals from the cable entries you intend using (paragraph 3.1 - [I]).
Note:
In order to guarantee the IP30 protection grade, do no remove any other seals.
5. Pull the cables through the open cable entries.
6. By means of the holes on the back of the cabinet, mount it to the wall (paragraph 3.1 - [G]).
Use anchor screws (stop screws) with 8mm diameter minimum.
7.
Insert and secure the various modules inside the cabinet and on the front plate.
8. Replace the front plate and reconnect the grounding conductor and CAN wire.
9. Complete the wiring of the internal modules.
4.2

Control panel wiring

Attention:
Take care to remove all sources of power, including the batteries before starting any wiring
operations.
Note:
The ends of wires must not be soft soldered in points where they are subject to clamping.
28
Fire detection control panel
Chapter 4
Installation

Publicidad

Tabla de contenido
loading

Tabla de contenido