4.5
Displayed Messages
Check for H <> X Cable Reversal
The DTR
may have detected a potentially hazardous step-up condition
®
while attempting to test the transformer as connected. Verify connections:
H
& H
RED
BLACK
X
should be attached to the low voltage winding.
BLACK
High Excitation Current
Check test cable connections for inadvertent short circuits. Check for
shorted transformer windings.
Check Cables & Connections
Verify that all test cable connections have been made correctly and are
firmly attached to the transformer terminals. Inspect transformer terminals
for dielectric coatings, fungus and corrosion.
Low Battery
Low battery indication. Recharge the batteries immediately.
Note: The DTR
Calibrating Please Wait
The DTR
always self-calibrates upon power-up. The DTR
®
automatically self-calibrate:
• at periodic intervals
• after 32 sequential test cycles have been performed
• following the detection of any error in which the DTR
cally cancels the test in progress
VT/PT Test Mode
Operation mode used in VT/PT testing, power-up default mode
VT/PT Test Mode Ready
Indicates system ready for VT/PT testing
CT Test Mode Selected
Indicates user selection of CT Test Mode. Mode selected by depressing
and holding TEST button during power-up sequence.
16
should be attached to the high voltage winding. X
can be operated during battery charging.
®
Digital Transformer Ratiometer DTR
&
RED
will also
®
automati-
®
Model 8500
®