Publicidad

Código de
Descripción
fallo
36
Overcurrent Inverter Phase L2, HW-
controlcard
37
Overcurrent Inverter Phase L2, Software
38
Overcurrent Phase L2, Software
39
Overcurrent Inverter Phase L3, HW-driver
40
Overcurrent Inverter Phase L3, HW-
controlcard
41
Overcurrent Inverter Phase L3, Software
42
Overcurrent Phase L3, Software
43
Overcurrent I_DC, HW-controlcard
44
Overcurrent I_DC, Software
45
UnsymmetryInverter currents
Sobretensión
70
Overvoltage Grid Phase L1, Stage 5
75
Overvoltage Grid Phase L2, Stage 5
80
Overvoltage Grid Phase L3, Stage 5
81
Overvoltage DC Link, HW-controlcard
82
Overvoltage DC Link, Software
Subtensión
120
Undervoltage Grid Phase L1, Stage 5
125
Undervoltage Grid Phase L2, Stage 5
130
Undervoltage Grid Phase L3, Stage 5
Disyuntor
Compruebe si los disyuntores están conectados: Disyuntor de CA Q2, interruptor seccionador de CC Q1.
151
Q1 Tripped
152
Q2 Tripped
155
K1 Tripped
Manual de instrucciones HSI500 / HSI640 / HSI1000 / HSI1250
Posible causa
Corriente de fase demasiado elevada
Corriente de fase L2 > 400 A
Corriente de red L2 > 180 A
Corriente de fase demasiado elevada
Corriente de fase demasiado elevada
Corriente de fase L3 > 400 A
Corriente de red L3 > 180 A
IDC demasiado elevada
IDC > 280 A
Tensión de red > 110 % o error de ajuste
Tensión de red > 110 % o error de ajuste
Tensión de red > 110 % o error de ajuste
Tensión CC > 900 V o error de ajuste
Tensión CC > 900 V o error de ajuste
Tensión de red < 90 %
Tensión de red < 90 %
Tensión de red < 90 %
- Interruptor seccionador de CC Q1 en
posición "tripped".
- ¿Está desbloqueado el interruptor de
parada de emergencia?
Interruptor seccionador de CA Q2 en
posición "tripped".
Interruptor principal de CA en posición
"tripped"
Averías