baltur TBG 45 PN Manual De Instrucciones página 8

Ocultar thumbs Ver también para TBG 45 PN:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 39
WORKING FIELD TBG 45PN / 60PN
E
N
G
L
mbar
I
10
S
8
H
6
4
2
0
100
10
2
4
The working fields are obtained from test boilers corresponding to the standard EN267 and are indicatively for the combination burner-
boiler. For correct working of the burner the size of the combustion chamber must correspond to current regulations; if not the manufac-
turers must be consulted.
POWER SUPPLY LINE
The gas supply scheme is shown in the diagram below. The gas train is certified in accordance with regulations EN 676 and is supplied
separately from the burner. A manual shut off valve and anti-vibration joint must be installed upstream of the gas valve, as shown in the
diagram.
GENERAL GAS BURNER SYSTEM
Legend
1) Manual shut off valve
2) Anti-vibration joint
3) Gas filter
4) Minimum gas pressure switch
5) Safety valve
6) Pressure regulator
7) Valves seal control device (obligatory for burner with maxi-
mum nominal thermal out-put over 1200 kW)
TBG 45P
TBG 45PN
TBG 45P-V
TBG 45ME
200
300
20
30
6
8
10
12
0006081367_201011
TBG 60P
TBG 60PN
TBG 60P-V
TBG 60ME
400
500
40
50
14
16
18
20
Gas train
supplied by the manufacturer
8) Two-stage working valve
9) Control servomotor
10) Air adjustment gate
11) Air pressure switch
12) Combustion head
6 / 18
kW
600
700
3
m /h(Metano)
n
60
70
3
m /h(G.P.L.)
n
22
24
26
28
The job of the installer

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Tbg 60 pn

Tabla de contenido