SMS -start SSV040 Manual De Uso página 11

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

SMS-start
can be connected either on the line that powers the motor (Fig. 1), or inside the delta
of the motor (Fig. 2), if you are using a motor with the windings connected in delta when powered
by mains voltage (i.e. 400/690 motor with 400V mains power or 230/400 motor with 230V mains
power).
When
SMS-start
is connected to the delta, the current passing through it (IF) is 1.6 times lower
than the line current (IL). It can therefore be used for motors with a rated current 1.6 times greater
rated current.
PICTURE. 1-CONNECTION ON LINE
TYPESMS-start
SSV040
SSV070
We suggest the connection of
power supply is removed the thermal memory, that allows different operating time according to
the absorbed current, is reset (see operating paragraph).
Without thermal memory the device is not able to be protected by any overload.
SMS-start
adapts automatically to the connection implemented and to the network phase se-
quence. In the event that it is necessary to reverse the motor rotation, it is sufficient to reverse
two supply phases between them (e.g. R with S), and consequently modify the connection of the
eventual PHASE CONTROL device, so that it keeps working fine.
IMPORTANT!
In the case of internal delta connection, it is necessary swap R with S and not
L1 with L2!
REV 4.1 Printed 09/2018
CONNECTIONS MOTOR
Connection on line
(Picture 1)
40
70
SMS-start
upstream of the contactors; (this is) because once that
CONTROL CIRCUITS CONNECTION
PICTURE. 2-INSIDE CONNECTION IN DELTA
MAX Motor Current
Connection on
delta (Picture 2)
65
115
SMS-start