5
Mount the air filter.
6
Close the air intake grille.
• In inverse process of 1, firmly attach the knob,
fixing bracket and fixing screw.
Air intake grille
knob
7
Turn on the circuit breaker, then push the
button on the remote controller to
start the operation.
8
After cleaning, push
.
display disappears.
CAUTION
• Do not start the air conditioner while leaving air filter
removed.
• Push the filter reset button. (
indication will be turn
off.)
39-EN
Cleaning of louver
The louver can be removed to clean if necessary.
1
Remove the louver.
• Holding both ends of the louver, remove it by
sagging the centre downwards.
2
Clean the louver with water.
• If dirt is heavy, clean the louver using tepid
water with neutral detergent or just water.
3
Mount the louver.
• First push in the one side, and insert the
opposite side by sagging the centre downwards.
(2) Insert in the louver sagging
down the centre downward.
(1) Insert
NOTE
Insert the louver in the correct direction.
Insert the louver with the printed mark facing upwards,
and the arrow on the louver pointing in the outward
direction.
▼ Periodic Maintenance
For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air conditioner
in use be cleaned and maintained regularly to ensure efficient operation of the air conditioner.
When the air conditioner is operated for a long time, periodic maintenance (once a year) is recommended.
Furthermore, regularly check the outdoor unit for rust and scratches, and remove them or apply rustproof
treatment, if necessary.
As a general rule, when an indoor unit is operated for 8 hours or more daily, clean the indoor unit and outdoor unit
at least once every 3 months. Ask a professional for this cleaning / maintenance work.
Such maintenance can extend the life of the product though it involves the owner's expense.
Failure to clean the indoor and outdoor units regularly will result in poor performance, freezing, water leakage, and
even compressor failure.
Inspection before maintenance
Following inspection must be carried out by a qualified installer or qualified service person.
Parts
Access from inspection opening and remove the access panel. Examine the heat exchanger if there
Heat exchanger
is any clogging or damages.
Fan motor
Access from inspection opening and check if any abnormal noise can be heard.
Access from inspection opening and remove the access panel. Examine the fan if there are any
Fan
waggles, damages or adhesive dust.
Filter
Go to installed location and check if there are any stains or breaks on the filter.
Access from inspection opening and remove the access panel. Check if there is any clogging or drain
Drain pan
water is polluted.
▼ Maintenance List
Part
Unit
Heat exchanger
Indoor / outdoor
Fan motor
Indoor / outdoor
Filter
Indoor
Fan
Indoor
Air intake / discharge
Indoor / outdoor
grilles
Drain pan
Indoor
Ornamental panel,
Indoor
louvres
Exterior
Outdoor
– 20 –
Inspection method
Check (visual / auditory)
Maintenance
Wash the heat exchanger when it is
Dust / dirt clogging, scratches
clogged.
Take appropriate measures when
Sound
abnormal sound is generated.
• Wash the filter with water when it is
contaminated.
Dust / dirt, breakage
• Replace it when it is damaged.
• Vibration, balance
• Replace the fan when vibration or
balance is terrible.
• Dust / dirt, appearance
• Brush or wash the fan when it is
contaminated.
Fix or replace them when they are
Dust / dirt, scratches
deformed or damaged.
Dust / dirt clogging, drain
Clean the drain pan and check the
contamination
downward slope for smooth drainage.
Wash them when they are contaminated
Dust / dirt, scratches
or apply repair coating.
• Rust, peeling of insulator
Apply repair coating.
• Peeling / lift of coat
40-EN