CAUTION
Bosch Power Tec GmbH
Terminal X21
Function
1/2
Auxiliary power supply L
3/4
Auxiliary power supply N
5/6
Auxiliary power supply PE
7/8
Connection for external switch to switch off the auxiliary power supply
(optional)
9/10
Connection (optional): If there is an external switching signal (230 V
mA) at terminals X21.9/10 ((Fuse board with test terminal block, p. 26))
and a switch-off command is issued to the central inverter, the central
inverter disconnects itself immediately from the grid.
1. Strip and remove the insulation from the cables
2. Connect wires L, N and PE.
Please note the following here:
The cables must be correctly allocated to the terminals
3. Route the cables below the cabinet support (2) and secure in place
4. Label the cables
Risk of injury due to damaged cable strain relief
Connection cables that are not strain-relieved may become damaged or
severed. This can result in serious personal injury or material damage.
Fit cable strain relief on-site
Use cable strain relief (cable support rail) to adequately secure
connection cables that enter the device
Only use aluminium or plastic cable clips for the cable strain relief. Check
all cable leads before connecting the cabling
5. Secure the cables on cable support rails
The auxiliary power supply is connected.
5.7

Connecting the CAN cable

Materials required
5-pin CAN cable with a 5-pin M12 receptacle on one side and a 5-pin M12
plug on the other side
Procedure
1. Assemble the CAN cable
Please note the following here:
Use the following cable: 5-pin CAN cable with a 5-pin M12 receptacle
on one side and a 5-pin M12 plug on the other side
Installation | 59
, 10
AC
BPT-C 200, 300, 350 | Operating manual