C7089U Outdoor Sensor
USE WITH TH8000 THERMOSTATS OR OTHER
COMPATIBLE HONEYWELL CONTROLS
APPLICATION
The C7089U Outdoor Sensor is compatible with
certain Honeywell thermostats and controllers, such
as the THX9421R Prestige thermostat with EIM,
TH8000 series RedLINK and Wi-Fi thermostats,
TH7000 series thermostat, TH6220U and TH6320U
models of the T6 Pro series thermostats, TH6220WF
and TH6320WF models of the Lyric T6 Wi-Fi series
thermostats, the HZ432 zone panel, and the H6062
HumidiPRO controller.
SPECIFICATIONS
Operating Ambient Temperature Range:
-40 to 120 °F (-40 to 49 °C).
Display Range:
-40 to 127 °F (-40 to 53 °C).
Sensor Accuracy:
+/-1.5 °F at 70 °F (+/-.84 °C at 21 °C)
Operating Relative Humidity:
5% to 95% non-condensing.
Dimensions in in. (mm):
2-1/4 (57) x 3/8 (10) with 60 (1524) leadwires.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to
follow them could damage the product or cause
a hazardous condition.
2. Check the ratings given in the instructions and
on the product to make sure the product is
suitable for your application.
INSTALLATION INSTRUCTIONS
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
CAUTION
Electrical Shock Hazard.
Can cause electrical shock or equipment
damage.
Disconnect power supply before connecting
wiring.
Location and Mounting (Fig. 1)
Mount the sensor where:
• cannot tamper with settings.
• there is good air circulation.
• it can measure true outdoor ambient temperature.
• surface is flat.
• wire distance between C7089U and thermostat is
less than 200 feet.
Do not mount the sensor:
• in direct sunlight.
• where hot or cold air blows on the sensor.
Discharge line from an outdoor compressor unit,
vent or fan causes inaccurate temperature
readings.
• where snow, ice or debris can cover it.
Use the following steps to mount the sensor:
1. Remove the sensor from the mounting clip.
2. Mark the area on the location selected for
mounting the sensor mounting clip.
3. Mount the clip.
69-1709EFS-03

Publicidad

Tabla de contenido
loading

Resumen de contenidos para Honeywell C7089U

  • Página 1 • it can measure true outdoor ambient temperature. Display Range: • surface is flat. -40 to 127 °F (-40 to 53 °C). • wire distance between C7089U and thermostat is Sensor Accuracy: less than 200 feet. +/-1.5 °F at 70 °F (+/-.84 °C at 21 °C)
  • Página 2 1. Wire the C7089U Outdoor Sensor to the appropriate S terminals on the thermostat or compatible device. If leadwire provided with C7089U is not long enough (60 in.), run a cable to a hole at C7089U location. a. Using color-coded, 18-gauge thermostat wire is recommended.
  • Página 3 126021 reading. -23.8 119493 To verify sensor resistance, remove one wire from one 113347 of the C7089U 60-in. leadwires. Use an ohmmeter to -28.9 106926 measure the resistance across the sensor. Then verify -27.8 100923 the sensor accuracy with the temperature/resistance in Table 1.
  • Página 4 28.9 8659 30.0 8315 31.1 7986 Home and Building Technologies In the U.S.: Honeywell 1985 Douglas Drive North ® U.S. Registered Trademark Golden Valley, MN 55422-3992 © 2017 Honeywell International Inc. 69-1709EFS—03 M.S. Rev. 06-17 customer.honeywell.com Printed in United States...
  • Página 5 -40 à 49 °C (-40 à 120 °F ). extérieure; • la surface est plate; Gamme d’affichage : • la distance du fil entre le C7089U et le thermostat -40 à 53 °C (-40 à 127 °F). est inférieure à 60 mètres. Précision : Ne pas installer le capteur : +/-0,84 °C à...
  • Página 6 1. Raccorder le capteur extérieur C7089U aux bornes S appropriées du thermostat ou du dispositif compatible. Si le conducteur fourni avec le C7089U n’est pas assez long (150 cm), faire passer un fil par une ouverture à l’endroit du C7089U.
  • Página 7 Le capteur extérieur C7089U convertit la température extérieure en une résistance lisible par le thermostat. Température extérieure Ohms de Le C7089U est à coefficient de température négatif, ce °F °C résistance qui signifie que la résistance diminue à mesure que la 195652 température augmente.
  • Página 8: Température Extérieure

    30.0 8315 31.1 7986 Home and Building Technologies Aux États-Unis : Honeywell 1985 Douglas Drive North ® Marque de commerce déposée aux États-Unis © 2017 Honeywell International Inc. Golden Valley, MN 55422 69-1709EFS—03 M.S. Rev. 06-17 Imprimé aux États-Unis customer.honeywell.com...
  • Página 9: Especificaciones

    Precisión del sensor: • la superficie sea plana. +/-1.5 °F a 70 °F (+/-.84 a 21 °C) • la distancia al cable entre el C7089U y el termostato sea menor de 200 pies (60 m). Humedad relativa de operación: 5 % a 95 % no condensante.
  • Página 10 1. Cablee el sensor exterior C7089U a las terminales S adecuadas en el termostato o dispositivo compatible. Si el cable guía incluido con el C7089U no es lo suficiente largo (60 pulgadas, 1.5 m), tienda un cable por un orificio en la ubicación del C7089U.
  • Página 11: Operación

    OPERACIÓN CALIBRACIÓN Cerciórese de configurar el termostato o el dispositivo El sensor exterior C7089U está calibrado en la fábrica compatible para un sensor exterior cableado de 10K y no se puede recalibrar en el campo. ohmios. Las opciones de configuración del instalador varían por modelo de termostato/dispositivo.
  • Página 12: Temperatura Exterior

    31.1 7986 Home and Building Technologies En los EE. UU.: Honeywell 1985 Douglas Drive North ® Marca Registrada en los Estados Unidos © 2017 Honeywell International Inc. Golden Valley, MN 55422 69-1709EFS—03 M.S. Rev. 06-17 Impreso en Estados Unidos customer.honeywell.com...

Tabla de contenido