Step 2: Exemplary settings for stand-alone mode
Example 1 is the factory setting (since factory settings are entered by computer, all
DIP switches of a new product are set to 'off').
DS-8 Ch. voltage
DS-7 Ch. voltage
DS-6 Absorpt. time
DS-5 Adaptive ch.
DS-4 Dyn. Curr. limit
DS-3 UPS function:
DS-2 Voltage
DS-1 Frequency
Step 2
Example 1 (factory setting):
8, 7 GEL 14,4V
6 Absorption time: 8 hours
5 Adaptive charging: on
4 Dynamic current limit: off
3 UPS function: on
2 Voltage: 230V
1 Frequency: 50Hz
To store the settings after the required values have been set: press the 'Down' button
for 2 seconds (lower button to the right of the DIP switches). The temperature and
low-battery LED's will flash to indicate acceptance of the settings.
You can then leave the DIP switches in the selected positions, so that the 'other
settings' can always be recovered.
32
off
DS-8
on
DS-7
on
DS-6
on
DS-5
off
DS-4
on
DS-3
on
DS-2
on
DS-1
Step 2
Example 2:
8, 7 OPzV 14,1V
6 Abs. time: 8 h
5 Adaptive ch.: on
4 Dyn. Curr. limit: off
3 UPS function: off
2 Voltage: 230V
1 Frequency: 50Hz
off
DS-8
off
DS-7
on
DS-6
on
DS-5
off
DS-4
off
DS-3
on
DS-2
on
DS-1
Step 2
Example 3:
8, 7 AGM 14,7V
6 Abs. time: 8 h
5 Adaptive ch: on
4 Dyn. Curr. limit: on
3 UPS function: off
2 Voltage: 240V
1 Frequency: 50Hz
on
DS-8
off
DS-7
on
DS-6
on
DS-5
on
DS-4
off
DS-3
off
DS-2
on
DS-1
Step 2
Example 4:
8, 7 Tub.-plate 15V
6 Abs. time: 4 h
5 Fixed abs. time
4 Dyn. Curr. limit: off
3 UPS function: on
2 Voltage: 240V
1 Frequency: 60Hz
on
on
off
off
off
on
off
off