Design of the electric drain heater:
3064055_201802.indd
GB
Notes on installation
Incorrectly performed electrical
installation work may result in
electrocution and damage to the
appliance.
When using a drain heater for the condensate pan, the outdoor unit must be
protected with a type B AC/DC-sensitive RCD. Type A RCDs are not suit-
able.
Protection by means of circuit breakers (automatic cut-outs) is not sufficient.
After installation, re-establish the contact protection.
The heat transfer of the condensate pan heater must not be impeded.
Please note
The heatable zone must only be installed in the metal zone.
Contact with plastic parts is not permitted.
When routing the heating cable, ensure that the apertures for the conden-
sate are not obstructed.
The installed thermostat ensures fully autonomous operation. It must not
be immersed.
The cable for the drain heater may not be shortened or damaged.
Do not route over sharp edges.
The bending radius must be no less than 20 mm.
Keep the cable away from the fan area.
When cleaning the condensate pan, only use detergents that are compat-
ible with silicone.
A = Unheated area, end marked 1x with
B = Heated area