WARNINGS AND CAUTIONS
• TO AVOID FIRE, SHOCK, OR DEATH; DISCONNECT POWER to all related circuits from power distribution system (or service) of building
before installing or servicing current transformers!
• TO AVOID OVERHEATING, DO NOT install a current transformer in an area where it would block ventilation openings.
• Power must be de-energized and the circuit opened in order to slip the CT over the power line.
• To be installed and/or used in accordance with appropriate electrical codes and regulations.
• If you are unsure about any part of these instructions, consult an electrician.
• Current transformers may not be installed in equipment where they exceed 75 percent of the wiring space of any cross-sectional area within the equipment.
• Installation is intended for Overvoltage Category IV or Service Entrance.
• DO NOT install a current transformer in area of breaker arc venting.
• Current transformers are not suitable for Class 2 wiring methods and are not intended for connection to Class 2 equipment.
• Secure current transformer and route conductors so that they do not directly contact live terminals or bus.
• Current transformer lead lengths may be extended up to 500 feet, although doing so may adversely affect the accuracy of meter readings. When extending lead lengths, use
twisted wires matching the gauge of the CT's attached leads and follow NEC and local electrical codes.
• If this equipment is used in a manner not specified by Leviton, the protection provided by the equipment may be impaired.
• For indoor use only.
NOTE: For complete installation instructions specific to the meter being installed, please refer to the meter installation guide.
DESCRIPTION
Leviton solid core CTs are accurate, cost effective and less susceptible to damage
during installation. Solid core CTs slip over power lines to measure the electrical current
flowing through the line. The CT "secondary" wires connect to the meter, facilitating
power and energy calculations.
Specifications
Operating ambient temperature rating
Relative humidity rating
Maximum Rated Voltage
Maximum Rated Current
100:0.1A CTs
200:0.1A CTs
Pollution Degree 2
Fig. 1
B
C
Dimensions / Dimensions / Dimensiones
A
CT Size/Rapport/Tamaño
100:0.1A
0.72"
(18.3mm)
200:0.1A
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper
use for five years from the purchase date. Leviton's only obligation is to correct such defects by repair or replacement, at its option. For details visit www.leviton.com or call 1-800-824-3005. This warranty
excludes and there is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused,
opened, abused, or altered in any manner, or is not used under normal operating conditions or not in accordance with any labels or instructions. There are no other or implied warranties of any kind, including
merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for a
particular purpose, is limited to five years. Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment,
lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
Leviton Solid Core Current Transformers
INSTALLATION INSTRUCTIONS
-30 to 55°C
90%
600V
Primary: 100A
Secondary: 110mA (0.11A)
Primary: 200A
Secondary: 110mA (0.11A)
Normally only non-conductive pollution
occurs. Occasionally, however, a temporary
conductivity caused by condensation must
be expected.
A
X1
X2
D
H1
B
C
2.06"
0.82"
(52.3mm)
(20.8mm)
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS
For Technical Assistance Call: 1-800-824-3005 (U.S.A. Only) www.leviton.com
Cat. Nos. CDA01, CDA02
INSTALLATION
WARNING: TO AVOID FIRE, SHOCK, OR DEATH; DISCONNECT POWER to all
related circuits from power distribution system (or service) of building before installing or
servicing current transformers!
1. Disconnect the conductor to be measured.
2. Insert the conductor through the center of the current transformer (CT).
The white case half identifies the H1 side, and should be oriented towards the
incoming LINE (Fig. 2).
NOTE: Ensure that the maximum current of the conductor does not exceed the
CT's rating.
3. Repeat Steps 1 and 2 if you are using more than one CT.
4. Connect the white wire on the CT to the positive terminal (+) on the measuring device.
5. Connect the colored wire (black, blue, red) on the CT to the negative (-) terminal
on the measuring device.
6. Reconnect the conductor and restore power.
7. You are now ready to begin your monitoring session.
Fig. 2
LINE / LIGNE / LÍNEA
L1
L2
CT1
CT2
D
48.00"
(1219mm)
LOAD / CHARGE / CARGA
L3
N
CT3
CT3
CT2 CT1
X1 X2 X1 X2 X1 X2
L3
L2
L1
PK-A3225-10-02-5A
ENGLISH